York AYK 550 User Manual page 234

Air modulators
Hide thumbs Also See for AYK 550:
Table of Contents

Advertisement

230
• Power Shield Cable – For power shield cable details, see "Motor Cable
Requirements for CE & C-Tick Compliance" below.
Grounding
See "Ground Connections" in "Input Power Connections" above.
For CE compliant installations and installations where EMC emissions must be
minimized, see "Effective Motor Cable Screens" below.
Drive's Motor Connection Terminals
The drive's motor and input power terminals have the same specifications. See
"Drive's Power Connection Terminals" above.
Motor Cable Requirements for CE & C-Tick Compliance
The requirements in this section apply for CE or C-Tick compliance.
Minimum Requirement (CE & C-Tick)
The motor cable must be a symmetrical three conductor cable with a concentric PE
conductor or a four conductor cable with a concentric shield, however, a symmetrical
constructed PE conductor is always recommended. The following figure shows the
minimum requirement for the motor cable screen (for example, MCMK, NK Cables).
Insulation Jacket
*
Input filters designed for AYK550 cannot be used in an isolated, or high impedance earthed
industrial distribution network.
Technical Data
Copper Wire Screen
Helix of Copper Tape
AYK550-UH User's Manual
Inner Insulation