Code Description
1106
REF2 SELECT
Selects the signal source for external reference
0...17 – Same as for parameter 1103
19 =
1
– The reference is taken from the
PID
OUT
19 =
1
PID
REF
SELECT
1...17
1107
REF2 MIN
Sets the minimum for external reference 2.
• The minimum analog input signal (in volts or amps) corresponds to
• Parameter 1301
• This parameter sets the minimum frequency reference.
• The value is a percentage of the:
– maximum frequency or speed
– maximum process reference
– nominal torque
1108
REF2 MAX
Sets the maximum for external reference 2.
• The maximum analog input signal (in volts or amps) corresponds to
• Parameter 1302
• This parameter sets the maximum frequency reference.
• The value is a percentage of the:
– maximum frequency or speed
– maximum process reference
– nominal torque
Start-Up
Group 11: Reference Select
Range
0...19
1
REF
SELECT
2
LIMIT
(1107, 1108)
MAX
(1107, 1108)
MIN
0.0...100.0%
(torque: 0...600%)
1 or 1304
MINIMUM AI
MINIMUM AI
0.0...100.0%
(torque: 0...600%)
1 or 1305
MAXIMUM AI
MAXIMUM AI
Resolution
1
2.
REF
.
1 output. See Groups 40 and 41.
PID
If PFA is used
PFA
0.1%
2
REF
2 sets the minimum analog input signal.
0.1%
2
REF
2 sets the maximum analog input signal.
AYK550-UH User's Manual
Default
19
0.0%
in %.
MIN
100.0%
in %.
MAX
S