D.5.7

Technical data of the temperature module

Mounting
Display
• Green "READY" LED
System interfaces
Sensor circuit
Conversion time
Type of connection
Typical sensor current:
• PT100
• PT1000/KTY83/KTY84/NTC
Open circuit detection/short-circuit
detection/measuring range:
• PT100/PT1000
• KTY83-110
• KTY84
• NTC
Measuring accuracy at an ambient
temperature of 20 °C (T20)
Deviation due to ambient
temperature (as % of measuring
range)
Isolation of the inputs to the
device electronics
Connection:
• Tightening torque
• Connection cross sections:
- Solid
- Finely stranded, with end sleeve
Table D-11: Technical data of the temperature module
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
Snap-on mounting onto 35 mm standard mounting rails or
screw attachment via additional plug-in lugs
• Continuous light: "Ready for operation"
• Flashing: "No connection to basic unit"
For connecting to a basic unit, an additional expansion
module, a current measuring module or a current/voltage
measuring module or the operator panel
500 ms
2 or 3-wire connection
1 mA (typical)
0.2 mA (typical)
Open circuit, short circuit; measuring range: -50 °C - +500 °C
Open circuit, short circuit; measuring range: -50 °C - +175 °C
Open circuit, short circuit; measuring range: -40 °C - +300 °C
Short circuit; measuring range: +80 °C - +160 °C
<+ 2 K
0.05 per K deviation from T20
No
TORQUE: 7 LB.IN - 10.3 LB.IN
0.8 Nm - 1.2 Nm
2
2
2x 0.5 mm
- 2.5 mm
/ 1x 0.5 mm
2 x AWG 20 to 14/1 x AWG 20 to 12
2
2
2x 0.5 mm
- 1.5 mm
/ 1x 0.5 mm
2 x AWG 20 to 16/1 x AWG 20 to 14
Technical data
2
2
- 4 mm
2
2
- 2.5 mm
D-21