Data Record 130 - Basic Device Parameters 1 - Siemens SIMOCODE pro System Manual

Motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

B.11

Data record 130 - Basic device parameters 1

Byte
Designation
Bit
(PRM group)
0.0
Reserved
4.0
Device configuration (12)
4.0
Device class
5.0
Thermistor (Th)
5.1
Reserved
6.0
Operator panel (OP or OPD)
6.1
Analog module (AM)
6.2
Temperature module (TM)
6.3
Earth-fault module (EM)
6.4
Digital module 1 (DM1)
6.6
Digital module 2 (DM2)
7.0
Reserved
8.0
Current measuring module
(IM/UM)
8.7
Voltage measuring module
(UM)
9.0
Reserved
10.0
Control function (CF)
11.0
Reserved
Table B-12: Data record 130 - Basic device parameters 1
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
Type
Range
De-
fault
Byte[4]
Byte[8]
Byte
5, 9
Bit
0, 1
Bit[7]
Bit
0, 1
Bit
0, 1
Bit
0, 1
Bit
0, 1
Bit[2]
0 .. 2
Bit[2]
0 .. 2
Bit[8]
Bit[7]
0 .. 5
Bit
0, 1
0x00
0x10
0x11
0x12
0x20
0x21
0x30
0x31
0x40
0x41
0x50
0x60
0x61
0x62
0x63
0x64
0x70
0x71
Bit[8]
Data formats and data records
Note
5 = BU1
9 = BU2
1 = active; thermistor in the BU
0 = no digital module
1 = monostable
2 = bistable
0 = no current measurement
1 = 0.3 A - 3 A
2 = 2.4 A - 25 A
3 = 10 A - 100 A
4 = 20 A - 200 A
5 = 63 A - 630 A
0x00 = Overload
0x10 = Direct starter
0x11 = Reversing starter
0x12 = Linked device
0x20 = Star-delta starter
0x21 = Star-delta
reversing starter
0x30 = Dahlander
0x31 = Dahlander
reversing starter
0x40 = Pole-changing starter
0x41 = Pole-changing
reversing starter
0x50 = Solenoid valve
0x60 = Positioner 1
0x61 = Positioner 2
0x62 = Positioner 3
0x63 = Positioner 4
0x64 = Positioner 5
0x70 = Soft starter
0x71 = Soft starter with
reversing contactor
Informa-
tion
BU1 BU2
BU1 BU2
BU2
BU1 BU2
BU1 BU2
BU2
BU2
BU2
BU2
BU2
BU1 BU2
BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU2
BU2
BU2
BU2
BU2
BU2
BU2
BU2
BU2
BU2
BU2
BU2
BU2
BU2
B-21