Monitoring functions
5.2.2
I> (upper limit)
Trip level, warning level
When monitoring current limits I> (upper limit), two different response levels
I> (upper limit) trip level, I> (upper limit) warning level can be parameterized
and monitored.
If the current of one or more phases exceeds the response level, current limit
monitoring responds.
Trip level:
Warning level:
Trip level and warning level activity
The trip level/warning level is only effective when the motor is running, the
start-up procedure has been completed and there is no test position
feedback (TPF) (run+).
Response at trip level
Here you can set how SIMOCODE pro should respond when the trip level is
overshot.
See also "Tables of responses of SIMOCODE pro" in
information".
Response
Deactivated
Signaling
Warning
Tripping
Delay
Table 5-3: "Warning level" response for monitoring current limits I>
Response at warning level
Here you can set how SIMOCODE pro should respond when the warning
level is overshot:
See also "Tables of responses of SIMOCODE pro" in
information".
Response
Deactivated
Signaling
Warning
Tripping
Delay
Table 5-4: "Warning level" response for monitoring current limits I>
Hysteresis
Here you can set the hysteresis for the current limits I> (upper limit):
Hysteresis
5-6
0 to 1020% of I
in 4% increments
s
0 to 1020% of I
in 4% increments
s
Trip level
X
X
-
X
0 - 25.5 s (0.5 s)
Warning level
X
X
X
-
0 - 25.5 s (0.5 s)
0 to 15% of the threshold value in 1% increments
Default: 5 %
Chapter "Important
Chapter "Important
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03