Technical Data; Basic Unit Rvs61.843 - Siemens Albatros2 User Manual

Heat pump controller
Hide thumbs Also See for Albatros2:
Table of Contents

Advertisement

Power supply
Wiring of terminals
Functional data
Inputs
Outputs
Siemens Switzerland Ltd
HVAC Products
8

Technical data

8.1

Basic unit RVS61.843

Rated voltage
Rated frequency
Power consumption
Fusing of supply lines
(Power supply and outputs)
Software class
Mode of operation to EN 60 730
Digital inputs H1, H3
Analog input H1, H3
Mains inputs EX1 – EX7,
E9 – E11
Sensor input B9
Sensor inuts B1, B3, B4, B21, B41,
B71, B81, B91 and B92
Sensor input BX1 – BX5
Perm. sensor cables (copper)
Cross-sectional area:
Max. length:
Relay outputs Q2, 3, 8, 9,
QX1 – QX6, Y1, Y2
Rated current range
Max. switch-on current
Max. total current (of all relays)
Rated voltage range
Output Q4-Mod
Rated current range
On / off mode
Speed control
Max. switch-on current
Analog output U1
Output voltage
Current rating
Ripple
Accuracy at zero point
Error remaining range
User manual RVS61.843
8 Technical data
AC 230 V ( ± 10%)
50/60 Hz
RVS61.843: max. 11 VA
Max. 10 AT
Solid wire or stranded wire (twisted or with
ferrule):
2
1 core: 0.5 mm
...2.5 mm
2
2 cores 0.5...1.5 mm
A
1b (automatic operation)
Safety extra low-voltage for potentialfree low-
voltage contacts:
Voltage with contact open: DC 12 V
Current with contact closed: DC 3 mA
Protective extra low-voltage operating range: DC
(0...10) V
Internal resistance: > 100 k Ω
AC 230 V ( ± 10%)
Internal resistance: > 100 k Ω
NTC1k (QAC34)
NTC10k (QAZ36, QAD36)
NTC 10k (QAZ36, QAD36), Pt1000
0.25 0.5
0.75 1.0
20
40
60
80
AC 0.02...2 (2) A
15 A for ≤ 1 s
AC 6 A
AC (24..230) V (for potentialfree outputs)
AC 0.05...2 (2) A
AC 0.05...0.4 (1) A
4 A for ≤ 1 s
Output is shortcircuit-proof
U
= 0 ... 10.0 V
out
± 2 mA RMS; ±2.7 mA peak
≦ 50 mVpp
< ± 80 mV
≦ 130 mV
2
1.5 (mm2)
120 (m)
205/221
CE1U2355en_02
23. November 2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents