Siemens SIMOCODE pro System Manual page 522

Motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Data formats and data records
Byte.
Designation
Bit
(PRM group)
12.0
Trip monitoring 0/4-20 mA>
12.2
Warning monitoring 0/4-20 mA>
12.4
Trip monitoring 0/4-20 mA<
12.6
Warning monitoring 0/4-20 mA<
13.0
Monitoring limit 1
13.2
Monitoring limit 2
13.4
Monitoring limit 3
13.6
Monitoring limit 4
14.0
Reserved
14.2
Reserved
14.4
Reserved
14.6
AM - Active inputs
15.0
DM - Delay inputs
15.2
AM - Response for open circuit
15.4
EM - Response to an external earth
fault
15.6
EM - Response to warning of an
external earth fault
16.0
Reserved
16.2
Reserved
16.4
DM-F - Test requirement response
16.6
DM-F - Safety-oriented tripping
response
17.0
TM - Trip response T>
17.2
TM - Warning response T>
17.4
TM - Response to a sensor fault/
out of range
17.6
TM - Active sensors
Table B-14: Data record 132 - Extended device parameters 1 (Cont.)
B-32
Type
Range
Bit[2]
0, 1, 2, 3
Bit[2]
0, 1, 2, 3
Bit[2]
0, 1, 2, 3
Bit[2]
0, 1, 2, 3
Bit[2]
0, 1, 2, 3
Bit[2]
0, 1, 2, 3
Bit[2]
0, 1, 2, 3
Bit[2]
0, 1, 2, 3
Bit[2]
Bit[2]
Bit[2]
Bit[2]
0, 1, 2
Bit[2]
0, 1, 2, 3
10 ms
Bit[2]
1, 2, 3
Bit[2]
1, 3
Bit[2]
0, 1, 2
Bit[2]
Bit[2]
Bit[2]
0, 1, 2
Bit[2]
0, 1, 2, 3
Bit[2]
1, 3
Bit[2]
0, 1, 2
Bit[2]
0, 1, 2, 3
Bit[2]
0, 1, 2
Unit
De-
Note
fault
0
0 = ON
(always)
0
1 = ON+
0
(always, not
0
TPF)
0
2 = RUN
(motor ON, not
0
TPF)
0
3 = RUN+
0
(motor ON, not
TPF,
start-up
override)
0
0
0
0
0 = 1 input
1 = 2 inputs
2 = 3 inputs
1
Offset 6ms
2
0 =
Deactivated
1
1 = Signaling
2 = Warning
0
3 = Tripping
0
0
0
0 =
Deactivated
0
1 = Signaling
2 = Warning
3
3 = Tripping
2
2
2
0 = 1 sensor
1 = 2 sensors
2= 3 sensors
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
Informa-
tion
AM
AM
AM
AM
BU2
BU2
BU2
BU2
AM
DM1 DM2
AM
EM
EM
DM-F
DM-F
TM
TM
TM
TM