Simocode Pro - Siemens SIMOCODE pro System Manual

Motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Mounting, wiring, interfaces
Basic unit pin assignment
The following table shows the pin assignment of the removable terminals:
Connection
Upper terminals
1
2
3
4
5
T2
6
7
8
9
10
T1
Lower terminals
A1
A2
A
B
SPE/PE
Table 13-4: Pin assignment for the removable terminals of the basic unit
Sequence for wiring the removable terminals for basic units
Proceed as follows:
Step
1
Connect the cables to the upper and lower terminals.
2
If you wish to use the A/B terminals for PROFIBUS DP , connect the
PROFIBUS DP cable-shielding to the SPE/PE terminal.
Notice
The A/B terminals are an alternative to the 9-pole SUB-D connection! Baud
rates of up to 1.5 MBit/s are possible!
3
Connect the system shielding to the SPE/PE terminal.
Table 13-5: Wiring the removable terminals of the basic unit
13-14
Assignment
Ground for relay outputs 1 and 2
Relay output OUT1
Relay output OUT2
Digital input IN3
Digital input IN4
Thermistor connection (binary PTC)
Relay output OUT3
Relay output OUT3
24 V DC only for IN1 to IN4
Digital input IN1
Digital input IN2
Thermistor connection (binary PTC)
Pin 1 supply voltage
Pin 2 supply voltage
PROFIBUS DP pin A
PROFIBUS DP pin B
System shielding
1
2
OUT1
.2
6
7
OUT3
24V
DEVICE
BUS
GEN. FAULT
TEST/
RESET
A1
A2
Description
GWA 4NEB 631 6050-22 DS 03
3
5
T2
4 IN3 IN4
8 9
10 T1
IN1 IN2
ϑ

SIMOCODE PRO

A
B SPE/PE
SIMOCODE pro

Advertisement

Table of Contents
loading