Products Solutions Services BA01718D/06/EN/03.19 71451449 2019-09-16 Valid as of version 01.01.zz (Device firmware) Operating Instructions Proline Promag H 300 PROFINET Electromagnetic flowmeter...
Page 2
• The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser Sales Center will supply you with current information and updates to these instructions. Endress+Hauser...
Proline Promag H 300 PROFINET Table of contents Table of contents About this document ....6 Installation ..... . . 21 Document function .
Page 4
Table of contents Proline Promag H 300 PROFINET 8.3.6 Navigating and selecting from list . . . 57 10.5.11 Configuring the local display ..103 8.3.7 Calling the parameter directly ..57 10.5.12 Configuring the low flow cut off .
Page 5
13.2 Measuring and test equipment ... 181 13.3 Endress+Hauser services ....181 Repair ......182 14.1 General notes .
About this document Proline Promag H 300 PROFINET About this document Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
Proline Promag H 300 PROFINET About this document Symbol Meaning Light emitting diode is on. Light emitting diode is flashing. 1.2.4 Tool symbols Symbol Meaning Flat blade screwdriver Allen key Open-ended wrench 1.2.5 Symbols for certain types of information Symbol...
• W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from nameplate • Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2D matrix code (QR code) on the nameplate Detailed list of the individual documents along with the documentation code →...
Proline Promag H 300 PROFINET Safety instructions Safety instructions Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
Proline Promag H 300 PROFINET Safety instructions IT security Our warranty is valid only if the device is installed and used as described in the Operating Instructions. The device is equipped with security mechanisms to protect it against any inadvertent changes to the settings.
Safety instructions Proline Promag H 300 PROFINET • User-specific access code Protect write access to the device parameters via the local display, Web browser or operating tool (e.g. FieldCare, DeviceCare). Access authorization is clearly regulated through the use of a user-specific access code.
Proline Promag H 300 PROFINET Safety instructions 2.7.4 Access via service interface (CDI-RJ45) The device can be connected to a network via the service interface (CDI-RJ45). Device- specific functions guarantee the secure operation of the device in a network. The use of relevant industrial standards and guidelines that have been defined by national and international safety committees, such as IEC/ISA62443 or the IEEE, is recommended.
Product description Proline Promag H 300 PROFINET Product description The device consists of a transmitter and a sensor. The device is available as a compact version: The transmitter and sensor form a mechanical unit. Product design N ic te r e rg ö...
Technical Documentation present? • If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. • Depending on the device version, the CD-ROM might not be part of the delivery! The Technical Documentation is available via the Internet or via the Endress+Hauser Operations App, see the "Product identification"...
8 sections • The W@M Device Viewer: enter the serial number from the nameplate (www.endress.com/deviceviewer) • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate. 4.2.1...
Proline Promag H 300 PROFINET Incoming acceptance and product identification 4.2.2 Sensor nameplate Order code: Ser. no.: Ext. ord. cd.: Date: A0029204 3 Example of sensor nameplate Name of the sensor Place of manufacture Order code Serial number (ser. no.) Extended order code (Ext.
Page 18
Incoming acceptance and product identification Proline Promag H 300 PROFINET 4.2.3 Symbols on measuring device Symbol Meaning WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. Reference to documentation Refers to the corresponding device documentation.
Proline Promag H 300 PROFINET Storage and transport Storage and transport Storage conditions Observe the following notes for storage: ‣ Store in the original packaging to ensure protection from shock. ‣ Do not remove protective covers or protective caps installed on process connections.
Storage and transport Proline Promag H 300 PROFINET 5.2.2 Measuring devices with lifting lugs CAUTION Special transportation instructions for devices with lifting lugs ‣ Only use the lifting lugs fitted on the device or flanges to transport the device. ‣...
Proline Promag H 300 PROFINET Installation Installation Installation conditions 6.1.1 Mounting position Mounting location A0029343 Preferably install the sensor in an ascending pipe, and ensure a sufficient distance to the next pipe elbow: h ≥ 2 × DN Installation in down pipes Install a siphon with a vent valve downstream of the sensor in down pipes whose length h ≥...
Page 22
Installation Proline Promag H 300 PROFINET Orientation The direction of the arrow on the sensor nameplate helps you to install the sensor according to the flow direction (direction of medium flow through the piping). Orientation Recommendation Vertical orientation A0015591 Horizontal orientation, transmitter at...
Proline Promag H 300 PROFINET Installation ≥ 5 × DN ≥ 2 × DN A0028997 Installation dimensions For the dimensions and installation lengths of the device, see the "Technical Information" document, "Mechanical construction" section. 6.1.2 Environment and process requirements Ambient temperature range Transmitter Standard: –40 to +60 °C (–40 to +140 °F)
Page 24
Installation Proline Promag H 300 PROFINET Vibrations L > 10 m (33 ft) A0029004 5 Measures to prevent vibration of the device In the event of very strong vibrations, the pipe and sensor must be supported and fixed. • Information on the shock resistance of the measuring system •...
Proline Promag H 300 PROFINET Installation 6.1.3 Special mounting instructions Protective cover 280 (11.0) 255 (10.0) 146 (5.75) 134 (5.3) 12 (0.47) 30 (1.18) A0029553 Sanitary compatibility When installing in hygienic applications, please refer to the information in the "Certificates and approvals/hygienic compatibility" section → 209.
Installation Proline Promag H 300 PROFINET – – 3 mm 4 mm A0029993 1. Depending on the device version: Loosen the securing clamp of the connection compartment cover. 2. Unscrew the connection compartment cover. 3. Release the fixing screw. 4. Turn the housing to the desired position.
Proline Promag H 300 PROFINET Installation Post-installation check Is the device undamaged (visual inspection)? Does the measuring device conform to the measuring point specifications? For example: • Process temperature • Process pressure (refer to the section on "Pressure-temperature ratings" in the "Technical Information"...
Electrical connection Proline Promag H 300 PROFINET Electrical connection NOTICE The measuring device does not have an internal circuit breaker. ‣ For this reason, assign the measuring device a switch or power-circuit breaker so that the power supply line can be easily disconnected from the mains.
Page 29
Proline Promag H 300 PROFINET Electrical connection Relay output Standard installation cable is sufficient. Current input 0/4 to 20 mA Standard installation cable is sufficient. Status input Standard installation cable is sufficient. Cable diameter • Cable glands supplied: M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in) •...
Page 30
Electrical connection Proline Promag H 300 PROFINET Max. cable length for use in Non-hazardous area, Cross-section Ex Zone 2, Class I, Division 2 Ex Zone 1, Class I, Division 1 0.34 mm (22 AWG) 80 m (270 ft) 0.50 mm...
Proline Promag H 300 PROFINET Electrical connection 7.1.3 Terminal assignment Transmitter: supply voltage, input/outputs The terminal assignment of the inputs and outputs depends on the individual order version of the device. The device-specific terminal assignment is documented on an adhesive label in the terminal cover.
Electrical connection Proline Promag H 300 PROFINET 2. If the measuring device is supplied without cable glands: Provide suitable cable gland for corresponding connecting cable. 3. If the measuring device is supplied with cable glands: Observe requirements for connecting cables → 28.
Page 33
Proline Promag H 300 PROFINET Electrical connection 4. Remove the display module holder. N ic N ic te r te r e rg ö ff e rg ö ff iz e iz e te n te n s io ri r...
Page 34
Electrical connection Proline Promag H 300 PROFINET Connecting the supply voltage and additional inputs/outputs 10 (0.4) mm (in) – A0033983 1. Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry.
Page 35
Proline Promag H 300 PROFINET Electrical connection Removing a cable 3 (0.12) A0029598 6 Engineering unit mm (in) 1. To remove a cable from the terminal, use a flat-blade screwdriver to push the slot between the two terminal holes 2.
Electrical connection Proline Promag H 300 PROFINET 7.2.2 Integrating the transmitter into a network This section only presents the basic options for integrating the device into a network. For information on the procedure to follow to connect the transmitter correctly → 32.
Page 37
Proline Promag H 300 PROFINET Electrical connection Integrating into a ring topology The device is integrated via the terminal connection for signal transmission (output 1) and the connection to the service interface (CDI-RJ45). Note the following when connecting: • Recommended cable: CAT5e, CAT6 or CAT7, with shielded connector (e.g. brand: YAMAICHI ;...
Electrical connection Proline Promag H 300 PROFINET 7.2.3 Connecting the remote display and operating module DKX001 The remote display and operating module DKX001 is available as an optional extra → 184. • The remote display and operating module DKX001 is only available for the following housing version: order code for "Housing": option A "Aluminum, coated"...
Page 39
• Grounding rings can be ordered separately as an accessory from Endress+Hauser . When ordering make sure that the grounding rings are compatible with the material used for...
Electrical connection Proline Promag H 300 PROFINET Special connection instructions 7.4.1 Connection examples PROFINET A0028767 7 Connection example for PROFINET Control system (e.g. PLC) Ethernet switch Observe cable specifications Device plug Transmitter PROFINET: MRP (Media Redundancy Protocol) A0027544 Control system (e.g. PLC) Ethernet switch Observe cable specifications →...
Page 41
Proline Promag H 300 PROFINET Electrical connection PROFINET: system redundancy S2 A0039553 8 Connection example for system redundancy S2 Control system 1 (e.g. PLC) Synchronization of control systems Control system 2 (e.g. PLC) Industrial Ethernet Managed Switch Transmitter Current output 4-20 mA 4...20 mA...
Page 42
Electrical connection Proline Promag H 300 PROFINET Pulse/frequency output 12345 A0028761 11 Connection example for pulse/frequency output (passive) Automation system with pulse/frequency input (e.g. PLC) Power supply Transmitter: Observe input values → 191 Switch output A0028760 12 Connection example for switch output (passive) Automation system with switch input (e.g.
Proline Promag H 300 PROFINET Electrical connection Current input A0028915 14 Connection example for 4 to 20 mA current input Power supply Terminal box External measuring device (to read in pressure or temperature, for instance) Transmitter Status input A0028764 ...
Page 44
Electrical connection Proline Promag H 300 PROFINET Setting the device name using the DIP switches The last part of the device name can be set using DIP switches 1-8. The address range is between 1 and 254 (factory setting: serial number of the device )
Proline Promag H 300 PROFINET Electrical connection 5. Reconnect the device to the power supply. The configured device address is used once the device is restarted. Setting the device name via the automation system DIP switches 1-8 must all be set to OFF (factory setting) or all be set to ON to be able to set the device name via the automation system.
Electrical connection Proline Promag H 300 PROFINET 4. Firmly tighten the cable glands. 5. To ensure that moisture does not enter the cable entry: Route the cable so that it loops down before the cable entry ("water trap"). A0029278 6.
Proline Promag H 300 PROFINET Operation options Operation options Overview of operation options A0034513 Local operation via display module Computer with Web browser (e.g. Internet Explorer) or with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX350 or SFX370...
Operation options Proline Promag H 300 PROFINET Structure and function of the operating menu 8.2.1 Structure of the operating menu For an overview of the operating menu for experts: "Description of Device Parameters" document supplied with the device→ 212...
Proline Promag H 300 PROFINET Operation options 8.2.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles (operator, maintenance etc.). Each user role contains typical tasks within the device lifecycle. Menu/parameter User role and tasks...
Operation options Proline Promag H 300 PROFINET Access to the operating menu via the local display 8.3.1 Operational display X X X X X X X 1120.50 A0029346 Operational display Device tag Status area Display area for measured values (4-line) Operating elements→...
Proline Promag H 300 PROFINET Operation options Measurement channel numbers Symbol Meaning Measurement channel 1 to 4 The measurement channel number is displayed only if more than one channel is present for the same measured variable type (e.g. Totalizer 1 to 3).
Page 52
Operation options Proline Promag H 300 PROFINET Status area The following appears in the status area of the navigation view in the top right corner: • In the submenu • The direct access code for the parameter you are navigating to (e.g. 0022-1) •...
Proline Promag H 300 PROFINET Operation options 8.3.3 Editing view Numeric editor +0.000 Xx – A0034250 17 For entering values in parameters (e.g. limit values) Entry display area Input screen Confirm, delete or reject entry Operating elements Text editor...
Page 54
Operation options Proline Promag H 300 PROFINET Operating key(s) Meaning Enter key • Press the key briefly: confirm your selection. • Press the key for 2 s: confirm the entry. Escape key combination (press keys simultaneously) Close the editing view without accepting the changes.
Proline Promag H 300 PROFINET Operation options 8.3.4 Operating elements Operating key(s) Meaning Minus key In a menu, submenu Moves the selection bar upwards in a picklist. With a Wizard Confirms the parameter value and goes to the previous parameter.
Page 56
Operation options Proline Promag H 300 PROFINET Calling up and closing the context menu The user is in the operational display. 1. Press the and keys for longer than 3 seconds. The context menu opens. XXXXXXXXXX Setup Conf.backup...
Proline Promag H 300 PROFINET Operation options 8.3.6 Navigating and selecting from list Different operating elements are used to navigate through the operating menu. The navigation path is displayed on the left in the header. Icons are displayed in front of the individual menus.
Operation options Proline Promag H 300 PROFINET The direct access code consists of a 5-digit number (at maximum) and the channel number, which identifies the channel of a process variable: e.g. 00914-2. In the navigation view, this appears on the right-hand side in the header of the selected parameter.
Proline Promag H 300 PROFINET Operation options Ent. access code Invalid or out of range input value Min:0 Max:9999 A0014049-EN For a description of the editing view - consisting of the text editor and numeric editor - with symbols → 53, for a description of the operating elements → 55 8.3.10...
Operation options Proline Promag H 300 PROFINET 2. Enter the access code. The -symbol in front of the parameters disappears; all previously write- protected parameters are now re-enabled. 8.3.12 Enabling and disabling the keypad lock The keypad lock makes it possible to block access to the entire operating menu via local operation.
Proline Promag H 300 PROFINET Operation options 8.4.2 Prerequisites Computer hardware Hardware Interface CDI-RJ45 WLAN Interface The computer must have an RJ45 The operating unit must have a interface. WLAN interface. Connection Standard Ethernet cable with RJ45 Connection via Wireless LAN.
Operation options Proline Promag H 300 PROFINET Measuring device: Via CDI-RJ45 service interface Device CDI-RJ45 service interface Measuring device The measuring device has an RJ45 interface. Web server Web server must be enabled; factory setting: ON For information on enabling the Web server → 66...
Page 63
Proline Promag H 300 PROFINET Operation options 4. If a 2nd network card is not used, close all the applications on the notebook. Applications requiring Internet or a network, such as e-mail, SAP applications, Internet or Windows Explorer. 5. Close any open Internet browsers.
Operation options Proline Promag H 300 PROFINET 2. Enter the IP address of the Web server in the address line of the Web browser: 192.168.1.212 The login page appears. 2 3 4 A0029417 Picture of device Device name Device tag...
Proline Promag H 300 PROFINET Operation options 8.4.5 User interface A0029418 Function row Local display language Navigation area Header The following information appears in the header: • Device name • Device tag • Device status with status signal → 146 •...
Operation options Proline Promag H 300 PROFINET Navigation area If a function is selected in the function bar, the submenus of the function open in the navigation area. The user can now navigate through the menu structure. Working area Depending on the selected function and the related submenus, various actions can be performed in this area: •...
Proline Promag H 300 PROFINET Operation options 3. If no longer needed: Reset modified properties of the Internet protocol (TCP/IP) → 62. If communication with the Web server was established via the default IP address 192.168.1.212, DIP switch No. 10 must be reset (from ON → OFF). Afterwards, the IP address of the device is active again for network communication.
Page 68
Operation options Proline Promag H 300 PROFINET A0033719 21 Options for remote operation via PROFINET network: ring topology Automation system, e.g. Simatic S7 (Siemens) Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or computer with operating tool (e.g.
Page 69
Proline Promag H 300 PROFINET Operation options A0034570 Transmitter with integrated WLAN antenna Transmitter with external WLAN antenna LED lit constantly: WLAN reception is enabled on measuring device LED flashing: WLAN connection established between operating unit and measuring device Computer with WLAN interface and Web browser (e.g. Microsoft Internet Explorer, Microsoft Edge) for accessing the integrated device Web server or with operating tool (e.g.
FieldCare Function scope FDT-based plant asset management tool from Endress+Hauser. It can configure all smart field devices in a system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition.
DeviceCare Function scope Tool to connect and configure Endress+Hauser field devices. The fastest way to configure Endress+Hauser field devices is with the dedicated "DeviceCare" tool. Together with the device type managers (DTMs) it presents a convenient, comprehensive solution. For details, see Innovation Brochure IN01047S...
Page 72
Operation options Proline Promag H 300 PROFINET Source for device description files See information → 73 Endress+Hauser...
Proline Promag H 300 PROFINET System integration System integration Overview of device description files 9.1.1 Current version data for the device Firmware version 01.01.zz • On the title page of the Operating instructions • On the transmitter nameplate • Firmware version Diagnostics →...
System integration Proline Promag H 300 PROFINET 9.2.1 File name of the device master file (GSD) Example of the name of a device master file: GSDML-V2.3.x-EH-PROMAG 300-yyyymmdd.xml GSDML Description language V2.3.x Version of the PROFINET specification Endress+Hauser PROMAG Instrument family...
Proline Promag H 300 PROFINET System integration Cyclic data transmission 9.3.1 Overview of the modules The following tables shows which modules are available to the measuring device for cyclic data exchange. Cyclic data exchange is performed with an automation system.
Page 76
System integration Proline Promag H 300 PROFINET Data structure Input data of Analog Input Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Measured value: floating point number (IEEE 754) Status Status coding → 81 Digital Input module Transmit digital input values from the measuring device to the automation system.
Page 77
Proline Promag H 300 PROFINET System integration Data structure Input data of Diagnose Input Byte 1 Byte 2 Byte 3 Byte 4 Diagnostic information number Status Value 0 Status Coding (hex) Status 0x00 No device error is present. Failure (F): 0x01 A device error is present.
Page 78
System integration Proline Promag H 300 PROFINET Selection: control totalizer Slot Sub-slot Value Control totalizer Totalize Reset + hold Preset + hold 11…13 Reset + totalize Preset + totalize Hold Data structure of output data (Totalizer Control submodule) Byte 1...
Page 79
Proline Promag H 300 PROFINET System integration Available units Density Temperature Unit code Unit Unit code Unit 1100 g/cm 1001 °C 1101 1002 °F 1099 kg/dm 1000 1103 kg/l 1003 °R 1097 kg/m 1628 SD4°C 1629 SD15°C 1630 SD20°C 32833 SG4°C...
Page 80
System integration Proline Promag H 300 PROFINET Digital Output module Transmit digital output values from the automation system to the measuring device. Digital output values are used by the automation system to enable and disable device functions. Digital output values cyclically transmit discrete output values, including the status, from the automation system to the measuring device.
Proline Promag H 300 PROFINET System integration Verification has failed Verification performed successfully (input data) Verification has not been performed – Verification control Start verification (output data) A change in the status from 0 to 1 starts the verification Data structure...
System integration Proline Promag H 300 PROFINET 9.3.4 Factory setting The slots are already assigned in the automation system for initial commissioning. Assigned slots Slot Factory setting Volume flow Mass flow Corrected volume flow Flow velocity 5…10 – Totalizer 1...
Proline Promag H 300 PROFINET System integration System redundancy S2 A redundant layout with two automation systems is necessary for processes that are in continuous operation. If one system fails the second system guarantees continued, uninterrupted operation. The measuring device supports S2 system redundancy and can communicate with both automation systems simultaneously.
Commissioning Proline Promag H 300 PROFINET Commissioning 10.1 Function check Before commissioning the measuring device: ‣ Make sure that the post-installation and post-connection checks have been performed. • "Post-installation check" checklist→ 27 • "Post-connection check" checklist → 46 10.2...
Proline Promag H 300 PROFINET Commissioning 10.5 Configuring the measuring device • The Setup menu with its guided wizards contains all the parameters needed for standard operation. • Navigation to the Setup menu X X X X X X X 20.50...
Proline Promag H 300 PROFINET Commissioning 10.5.4 Selecting and setting the medium The Select medium wizard submenu contains parameters that must be configured in order to select and set the medium. Navigation "Setup" menu → Select medium ‣ Medium selection →...
Commissioning Proline Promag H 300 PROFINET Apply I/O configuration → 90 I/O alteration code → 90 Parameter overview with brief description Parameter Description User interface / Selection / Factory setting User entry I/O module 1 to n terminal numbers Shows the terminal numbers used by the I/O •...
Proline Promag H 300 PROFINET Commissioning Failure mode → 91 Failure value → 91 Parameter overview with brief description Parameter Prerequisite Description User interface / Factory setting Selection / User entry Terminal number – Shows the terminal numbers • Not used –...
Commissioning Proline Promag H 300 PROFINET Terminal number → 92 Response time status input → 92 Terminal number → 92 Parameter overview with brief description Parameter Description User interface / Selection / Factory setting User entry Terminal number Shows the terminal numbers used by the •...
Page 93
Proline Promag H 300 PROFINET Commissioning Failure mode → 94 Failure current → 94 Parameter overview with brief description Parameter Prerequisite Description User interface / Factory setting Selection / User entry Terminal number – Shows the terminal numbers • Not used –...
Page 94
Commissioning Proline Promag H 300 PROFINET Parameter Prerequisite Description User interface / Factory setting Selection / User entry 20 mA value One of the following options is Enter 20 mA value. Signed floating-point Depends on country selected in the Current span number and nominal parameter (→...
Proline Promag H 300 PROFINET Commissioning 10.5.9 Configuring the pulse/frequency/switch output The Pulse/frequency/switch output wizard guides you systematically through all the parameters that can be set for configuring the selected output type. Navigation "Setup" menu → Advanced setup → Pulse/frequency/switch output ‣...
Page 96
Commissioning Proline Promag H 300 PROFINET Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Operating mode – Define the output as a pulse, • Pulse Pulse frequency or switch output. • Frequency • Switch Terminal number –...
Page 97
Proline Promag H 300 PROFINET Commissioning Minimum frequency value → 98 Maximum frequency value → 98 Measuring value at minimum → 98 frequency Measuring value at maximum → 98 frequency → 98 Failure mode Failure frequency →...
Page 98
Commissioning Proline Promag H 300 PROFINET Parameter Prerequisite Description Selection / User Factory setting interface / User entry Minimum frequency value The Frequency option is Enter minimum frequency. 0.0 to 10 000.0 Hz 0.0 Hz selected in the Operating mode parameter (→ 95)
Page 99
Proline Promag H 300 PROFINET Commissioning Configuring the switch output Navigation "Setup" menu → Pulse/frequency/switch output ‣ Pulse/frequency/switch output 1 to n Operating mode → 99 Terminal number → 99 Signal mode → 99 → 100...
Page 100
Commissioning Proline Promag H 300 PROFINET Parameter Prerequisite Description Selection / User Factory setting interface / User entry Switch output function The Switch option is selected Select function for switch • Off in the Operating mode output. • On parameter. • Diagnostic behavior • Limit •...
Proline Promag H 300 PROFINET Commissioning Parameter Prerequisite Description Selection / User Factory setting interface / User entry Switch-off delay • The Switch option is Define delay for the switch-off 0.0 to 100.0 s 0.0 s selected in the Operating of status output. mode parameter.
Page 102
Commissioning Proline Promag H 300 PROFINET Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting interface / User entry Relay output function – Select the function for the • Closed Closed relay output. • Open • Diagnostic behavior • Limit •...
Proline Promag H 300 PROFINET Commissioning 10.5.11 Configuring the local display The Display wizard guides you systematically through all the parameters that can configured for configuring the local display. Navigation "Setup" menu → Display ‣ Display Format display → 104 Value 1 display →...
Page 104
Commissioning Proline Promag H 300 PROFINET Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Format display A local display is provided. Select how measured values • 1 value, max. size 1 value, max. size are shown on the display.
Page 105
Proline Promag H 300 PROFINET Commissioning Parameter Prerequisite Description Selection / User Factory setting entry Value 2 display A local display is provided. Select the measured value that • None None is shown on the local display. • Volume flow • Mass flow •...
Commissioning Proline Promag H 300 PROFINET Parameter Prerequisite Description Selection / User Factory setting entry 100% bargraph value 3 A selection was made in the Enter 100% value for bar Signed floating-point Value 3 display parameter. graph display. number Value 4 display A local display is provided.
Page 107
Proline Promag H 300 PROFINET Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Assign process variable – Select process variable for low • Off Volume flow flow cut off. • Volume flow • Mass flow •...
Commissioning Proline Promag H 300 PROFINET 10.5.13 Configuring empty pipe detection The Empty pipe detection submenu contains parameters that must be configured for the configuration of empty pipe detection. Navigation "Setup" menu → Empty pipe detection ‣ Empty pipe detection →...
Proline Promag H 300 PROFINET Commissioning 10.6 Advanced settings The Advanced setup submenu together with its submenus contains parameters for specific settings. Navigation to the "Advanced setup" submenu X X X X X X X 20.50 0104-1 Main menu Display language English Display/operat.
Commissioning Proline Promag H 300 PROFINET 10.6.4 Carrying out additional display configurations In the Display submenu you can set all the parameters associated with the configuration of the local display. Navigation "Setup" menu → Advanced setup → Display ‣ Display →...
Page 113
Proline Promag H 300 PROFINET Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection / User Factory setting entry Format display A local display is provided. Select how measured values • 1 value, max. size 1 value, max. size are shown on the display.
Page 114
Commissioning Proline Promag H 300 PROFINET Parameter Prerequisite Description Selection / User Factory setting entry Value 2 display A local display is provided. Select the measured value that • None None is shown on the local display. • Volume flow • Mass flow •...
Page 115
Proline Promag H 300 PROFINET Commissioning Parameter Prerequisite Description Selection / User Factory setting entry 0% bargraph value 3 A selection was made in the Enter 0% value for bar graph Signed floating-point Country-specific: Value 3 display parameter. display. number • 0 l/h •...
Commissioning Proline Promag H 300 PROFINET Parameter Prerequisite Description Selection / User Factory setting entry Display language A local display is provided. Set display language. • English English • Deutsch (alternatively, the • Français ordered language is • Español preset in the device) •...
Proline Promag H 300 PROFINET Commissioning Parameter Prerequisite Description Selection / User Factory setting entry / User interface WLAN password – Enter WLAN password. – – WLAN IP address – Enter IP address of the WLAN 4 octet: 0 to 255 (in 192.168.1.212 interface of the device.
Commissioning Proline Promag H 300 PROFINET Parameter overview with brief description Parameter Description User interface / Selection Factory setting Operating time Indicates how long the device has been in Days (d), hours (h), minutes – operation. (m) and seconds (s) Last backup...
Page 121
Proline Promag H 300 PROFINET Commissioning Navigation "Setup" menu → Advanced setup → Administration ‣ Administration ‣ → 121 Define access code ‣ → 121 Reset access code Device reset → 122 Using the parameter to define the access code Navigation "Setup"...
Commissioning Proline Promag H 300 PROFINET Parameter overview with brief description Parameter Description User interface / User entry Factory setting Operating time Indicates how long the device has been in Days (d), hours (h), minutes – operation. (m) and seconds (s) Reset access code Reset access code to factory settings.
Page 123
Proline Promag H 300 PROFINET Commissioning Current output 1 to n simulation → 124 Value current output 1 to n → 124 Frequency output simulation 1 to n → 124 Frequency value 1 to n → 124 →...
Page 124
Commissioning Proline Promag H 300 PROFINET Parameter Prerequisite Description Selection / User Factory setting entry / User interface Value current input 1 to n In the Current input 1 to n Enter the current value for 0 to 22.5 mA 0 mA simulation parameter, the On simulation.
Proline Promag H 300 PROFINET Commissioning Parameter Prerequisite Description Selection / User Factory setting entry / User interface Diagnostic event simulation – Select a diagnostic event to • Off simulate this event. • Diagnostic event picklist (depends on the category selected) Logging interval –...
Via Web browser, FieldCare, DeviceCare (via CDI-RJ45 service interface), fieldbus For a reset code, contact your Endress+Hauser service organization. 1. Navigate to the Reset access code parameter (→ 122). 2. Enter the reset code.
Page 127
Proline Promag H 300 PROFINET Commissioning A0029630 Setting the write protection (WP) switch on the main electronics module to the ON position enables hardware write protection. In the Locking status parameter the Hardware locked option is displayed → 128. In addition, on the local display the -symbol appears in front of the parameters in the header of the operational display and in the navigation view.
Operation Proline Promag H 300 PROFINET Operation 11.1 Reading the device locking status Device active write protection: Locking status parameter Operation → Locking status Function scope of the "Locking status" parameter Options Description None The access status displayed in the Access status parameter applies → 59. Only appears on local display.
Proline Promag H 300 PROFINET Operation 11.4.1 "Process variables" submenu The Process variables submenu contains all the parameters needed to display the current measured values for each process variable. Navigation "Diagnostics" menu → Measured values → Process variables ‣ Process variables...
Operation Proline Promag H 300 PROFINET Parameter Prerequisite Description User interface Corrected conductivity One of the following conditions is met: Displays the conductivity currently Positive floating-point • Order code for "Sensor option", option corrected. number CI "Medium temperature Dependency measurement"...
Operation Proline Promag H 300 PROFINET Navigation "Diagnostics" menu → Measured values → Input values → Current input 1 to n ‣ Current input 1 to n → 132 Measured values 1 to n → 132 Measured current 1 to n...
Page 133
Proline Promag H 300 PROFINET Operation ‣ Pulse/frequency/switch output → 133 1 to n ‣ Relay output 1 to n → 134 Output values of current output The Value current output submenu contains all the parameters needed to display the current measured values for every current output.
Operation Proline Promag H 300 PROFINET Parameter overview with brief description Parameter Prerequisite Description User interface Output frequency 1 to n In the Operating mode parameter, the Displays the value currently measured 0.0 to 12 500.0 Hz Frequency option is selected.
Proline Promag H 300 PROFINET Operation Navigation "Operation" menu → Totalizer handling ‣ Totalizer handling → 135 Control Totalizer 1 to n → 135 Preset value 1 to n Reset all totalizers → 135 Parameter overview with brief description...
Operation Proline Promag H 300 PROFINET 11.7 Showing data logging The Extended HistoROM application package must be enabled in the device (order option) for the Data logging submenu to appear. This contains all the parameters for the measured value history.
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostics and troubleshooting 12.1 General troubleshooting For local display Error Possible causes Solution Local display dark and no output Supply voltage does not match the Apply the correct supply voltage . signals value indicated on the nameplate.
Page 140
Diagnostics and troubleshooting Proline Promag H 300 PROFINET For access Error Possible causes Solution No write access to parameters Hardware write protection enabled Set the write protection switch on main electronics module to the OFF position → 126. No write access to parameters Current user role has limited access 1.
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Error Possible causes Solution Not connecting to Web server, No WLAN network available • Check if WLAN reception is FieldCare or DeviceCare present: LED on display module is lit blue • Check if WLAN connection is...
Page 142
Diagnostics and troubleshooting Proline Promag H 300 PROFINET 1 2 3 4 5 A0029629 Supply voltage Device status Flashing/network status Port 1 active: PROFINET Port 2 active: PROFINET and service interface (CDI) Color Meaning Supply voltage Supply voltage is off or too low.
Proline Promag H 300 PROFINET Diagnostics and troubleshooting 12.3 Diagnostic information on local display 12.3.1 Diagnostic message Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the operational display. Operational display in alarm condition...
Page 144
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic behavior Symbol Meaning Alarm • Measurement is interrupted. • Signal outputs and totalizers assume the defined alarm condition. • A diagnostic message is generated. Warning Measurement is resumed. The signal outputs and totalizers are not affected. A diagnostic message is generated.
Proline Promag H 300 PROFINET Diagnostics and troubleshooting 12.3.2 Calling up remedial measures X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2...
Diagnostics and troubleshooting Proline Promag H 300 PROFINET A0031056 Status area with status signal Diagnostic information Remedy information with Service ID In addition, diagnostic events which have occurred can be shown in the Diagnostics menu: • Via parameter → 175 •...
Diagnostics and troubleshooting Proline Promag H 300 PROFINET 12.6 Adapting the diagnostic information 12.6.1 Adapting the diagnostic behavior Each item of diagnostic information is assigned a specific diagnostic behavior at the factory. The user can change this assignment for specific diagnostic information in the Diagnostic behavior submenu.
Page 149
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Supported status information Status Coding (hex) BAD - Maintenance alarm 0x24 BAD - Process related 0x28 BAD - Function check 0x3C UNCERTAIN - Initial value 0x4F UNCERTAIN - Maintenance demanded 0x68 UNCERTAIN - Process related...
Page 150
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Measured value status (fixed assignment) Diagnostic behavior Device diagnosis Quality Coding Category (configurable) (fixed assignment) Quality Substatus (hex) (NE107) Logbook entry only GOOD 0x80 to 0x8E – – Diagnostic information 302 Measured value status (fixed assignment)
Proline Promag H 300 PROFINET Diagnostics and troubleshooting 12.7 Overview of diagnostic information The amount of diagnostic information and the number of measured variables affected increase if the measuring device has one or more application packages. In the case of some items of diagnostic information, the diagnostic behavior can be changed.
Page 152
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic information Remedy instructions Influenced measured variables Short text 083 Memory content 1. Restart device • Conductivity 2. Restore HistoROM S-DAT backup • Corrected conductivity Measured variable status (' D evice reset' parameter) •...
Page 153
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostic information Remedy instructions Influenced measured variables Short text 170 Coil resistance Check ambient and process temperature • Conductivity • Corrected conductivity Measured variable status • Density • Electronic temperature Quality • Flow velocity...
Diagnostics and troubleshooting Proline Promag H 300 PROFINET 12.7.2 Diagnostic of electronic Diagnostic information Remedy instructions Influenced measured variables Short text 201 Device failure 1. Restart device • Conductivity 2. Contact service • Corrected conductivity Measured variable status • Measured values 1 •...
Page 155
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostic information Remedy instructions Influenced measured variables Short text 252 Modules incompatible 1. Check if correct electronic modul is • Conductivity plugged • Corrected conductivity Measured variable status 2. Replace electronic module •...
Page 156
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic information Remedy instructions Influenced measured variables Short text 271 Main electronic failure 1. Restart device • Conductivity 2. Change main electronic module • Corrected conductivity Measured variable status • Measured values 1 •...
Page 157
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostic information Remedy instructions Influenced measured variables Short text 275 I/O module 1 to n defective Change I/O module • Conductivity • Corrected conductivity Measured variable status • Measured values 1 • Measured values 2 Quality •...
Page 158
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic information Remedy instructions Influenced measured variables Short text 302 Device verification active Device verification active, please wait. • Conductivity • Corrected conductivity Measured variable status [from the factory] • Measured values 1 •...
Page 159
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostic information Remedy instructions Influenced measured variables Short text 332 Writing in HistoROM backup failed Replace user interface board • Conductivity Ex d/XP: replace transmitter • Corrected conductivity Measured variable status • Measured values 1 •...
Page 160
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic information Remedy instructions Influenced measured variables Short text 373 Sensor electronic (ISEM) faulty 1. Transfer data or reset device • Conductivity 2. Contact service • Corrected conductivity Measured variable status • Measured values 1 •...
Page 161
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostic information Remedy instructions Influenced measured variables Short text 376 Sensor electronic (ISEM) faulty 1. Replace sensor electronic module • Conductivity (ISEM) • Corrected conductivity Measured variable status [from the factory] 2. Turn off diagnostic message •...
Page 162
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic information Remedy instructions Influenced measured variables Short text 382 Data storage 1. Insert T-DAT • Conductivity 2. Replace T-DAT • Corrected conductivity Measured variable status • Measured values 1 • Measured values 2 Quality •...
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostic information Remedy instructions Influenced measured variables Short text 512 Sensor electronic (ISEM) faulty 1. Check ECC recovery time • Conductivity 2. Turn off ECC • Corrected conductivity Measured variable status • Density •...
Page 164
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic information Remedy instructions Influenced measured variables Short text 410 Data transfer 1. Check connection • Conductivity 2. Retry data transfer • Corrected conductivity Measured variable status • Measured values 1 • Measured values 2 Quality •...
Page 165
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostic information Remedy instructions Influenced measured variables Short text 437 Configuration incompatible 1. Restart device • Conductivity 2. Contact service • Corrected conductivity Measured variable status • Measured values 1 • Measured values 2 Quality •...
Page 166
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic information Remedy instructions Influenced measured variables Short text 442 Frequency output 1 to n 1. Check process – 2. Check frequency output settings Measured variable status [from the factory] Quality Good...
Page 167
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostic information Remedy instructions Influenced measured variables Short text 453 Flow override Deactivate flow override • Conductivity • Corrected conductivity Measured variable status • Density • Electronic temperature Quality Good • Flow velocity...
Page 168
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic information Remedy instructions Influenced measured variables Short text 486 Current input 1 to n simulation Deactivate simulation • Measured values 1 • Measured values 2 Measured variable status • Measured values 3...
Page 169
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostic information Remedy instructions Influenced measured variables Short text 494 Switch output simulation 1 to n Deactivate simulation switch output – Measured variable status Quality Good Quality substatus Coding (hex) 0x80 to 0x83...
Page 170
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic information Remedy instructions Influenced measured variables Short text 520 I/O 1 to n hardware configuration invalid 1. Check I/O hardware configuration – 2. Replace wrong I/O module Measured variable status 3. Plug the module of double pulse output...
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostic information Remedy instructions Influenced measured variables Short text 594 Relay output simulation Deactivate simulation switch output – Measured variable status Quality Good Quality substatus Coding (hex) 0x80 to 0x83 Status signal...
Page 172
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic information Remedy instructions Influenced measured variables Short text 833 Electronic temperature too low Increase ambient temperature • Conductivity • Corrected conductivity Measured variable status [from the factory] • Measured values 1 •...
Page 173
Proline Promag H 300 PROFINET Diagnostics and troubleshooting Diagnostic information Remedy instructions Influenced measured variables Short text 842 Process limit Low flow cut off active! • Flow velocity 1. Check low flow cut off configuration • Mass flow Measured variable status [from the factory] •...
Page 174
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Diagnostic information Remedy instructions Influenced measured variables Short text 938 EMC interference 1. Check ambient conditions regarding • Conductivity EMC influence • Corrected conductivity Measured variable status [from the factory] 2. Turn off diagnostic message •...
Proline Promag H 300 PROFINET Diagnostics and troubleshooting 12.8 Pending diagnostic events The Diagnostics menu allows the user to view the current diagnostic event and the previous diagnostic event separately. To call up the measures to rectify a diagnostic event: •...
Diagnostics and troubleshooting Proline Promag H 300 PROFINET / ../Diagnose list Diagnostics F273 Main electronic Diagnostics 2 Diagnostics 3 A0014006-EN 29 Taking the example of the local display To call up the measures to rectify a diagnostic event: • Via local display → 145 •...
Proline Promag H 300 PROFINET Diagnostics and troubleshooting 12.10.2 Filtering the event logbook Using the Filter options parameter you can define which category of event message is displayed in the Events list submenu. Navigation path Diagnostics → Event logbook → Filter options Filter categories •...
Diagnostics and troubleshooting Proline Promag H 300 PROFINET Info number Info name I1514 Upload started I1515 Upload finished I1618 I/O module 2 replaced I1619 I/O module 3 replaced I1621 I/O module 4 replaced I1622 Calibration changed I1624 Reset all totalizers...
Proline Promag H 300 PROFINET Diagnostics and troubleshooting 12.12 Device information The Device information submenu contains all parameters that display different information for device identification. Navigation "Diagnostics" menu → Device information ‣ Device information Device tag → 179 → 179...
"Manufacturer' s information" document. The manufacturer' s information is available: • In the Download Area of the Endress+Hauser web site: www.endress.com → Downloads • Specify the following details: • Product root: e.g. 5H3B The product root is the first part of the order code: see the nameplate on the device.
Replacement seals (accessory part) → 211 13.2 Measuring and test equipment Endress+Hauser offers a wide variety of measuring and test equipment, such as W@M or device tests. Your Endress+Hauser Sales Center can provide detailed information on the services. List of some of the measuring and testing equipment: → 184 13.3...
• The measuring devices have a modular design. • Spare parts are grouped into logical kits with the associated Installation Instructions. • Repairs are carried out by Endress+Hauser Service or by appropriately trained customers. • Certified devices can only be converted to other certified devices by Endress+Hauser Service or at the factory.
Proline Promag H 300 PROFINET Repair WARNING Danger to persons from process conditions. ‣ Beware of hazardous process conditions such as pressure in the measuring device, high temperatures or aggressive fluids. 2. Carry out the mounting and connection steps from the "Mounting the measuring device"...
Various accessories, which can be ordered with the device or subsequently from Endress +Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
Proline Promag H 300 PROFINET Accessories 15.1.2 For the sensor Accessories Description Adapter set Adapter connections for installing a Promag H instead of a Promag 30/33 A or Promag 30/33 H (DN 25). Consists of: • 2 process connections • Screws •...
Accessories Description Applicator Software for selecting and sizing Endress+Hauser measuring devices: • Choice of measuring devices for industrial requirements • Calculation of all the necessary data for identifying the optimum flowmeter: e.g. nominal diameter, pressure loss, flow velocity and accuracy.
Proline Promag H 300 PROFINET Technical data Technical data 16.1 Application The measuring device is only suitable for flow measurement of liquids with a minimum conductivity of 5 µS/cm. Depending on the version ordered, the measuring device can also measure potentially explosive, flammable, poisonous and oxidizing media.
Page 188
Technical data Proline Promag H 300 PROFINET Recommended Nominal diameter Factory settings flow min./max. full Full scale value Pulse value Low flow cut off scale value current output (~ 2 pulse/s) (v ~ 0.04 m/s) (v ~ 0.3/10 m/s) (v ~ 2.5 m/s)
Page 189
• Reference density for calculating the mass flow Various pressure transmitters and temperature measuring devices can be ordered from Endress+Hauser: see "Accessories" section → 186 It is recommended to read in external measured values to calculate the corrected volume flow.
Page 190
Technical data Proline Promag H 300 PROFINET Input signal level • Low signal: DC –3 to +5 V • High signal: DC 12 to 30 V Assignable functions • Off • Reset the individual totalizers separately • Reset all totalizers •...
Proline Promag H 300 PROFINET Technical data 16.4 Output Output signal PROFINET Standards In accordance with IEEE 802.3 Current output 4 to 20 mA Signal mode Can be set to: • Active • Passive Current range Can be set to: •...
Page 192
Technical data Proline Promag H 300 PROFINET Assignable measured • Volume flow variables • Mass flow • Corrected volume flow Frequency output Maximum input values DC 30 V, 250 mA (passive) Maximum output current 22.5 mA (active) Open-circuit voltage DC 28.8 V (active)
Page 193
Proline Promag H 300 PROFINET Technical data Maximum switching • DC 30 V, 0.1 A capacity (passive) • AC 30 V, 0.5 A Assignable functions • Off • On • Diagnostic behavior • Limit value: • Off • Volume flow •...
Page 194
Technical data Proline Promag H 300 PROFINET Pulse/frequency/switch output Pulse output Failure mode Choose from: • Actual value • No pulses Frequency output Failure mode Choose from: • Actual value • 0 Hz • Defined value (f 2 to 12 500 Hz)
Page 195
Proline Promag H 300 PROFINET Technical data Light emitting diodes (LED) Status information Status indicated by various light emitting diodes The following information is displayed depending on the device version: • Supply voltage active • Data transmission active • Device alarm/error has occurred •...
Technical data Proline Promag H 300 PROFINET Supported functions • Identification & Maintenance Simple device identification via: • Control system • Nameplate • Measured value status The process variables are communicated with a measured value status • Blinking feature via the onsite display for simple device identification and assignment •...
Proline Promag H 300 PROFINET Technical data terminals Spring-loaded terminals: Suitable for strands and strands with ferrules. Conductor cross-section 0.2 to 2.5 mm (24 to 12 AWG). Cable entries • Cable gland: M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in) •...
Technical data Proline Promag H 300 PROFINET Temperature ±0.5 °C (±0.9 °F) Electrical conductivity • Max. ±5 % o.r. • Max. ±1 % o.r. for DN 15 to 150 in conjunction with stainless steel process connections, 1.4404 (F316L) Temperature measurement <...
Proline Promag H 300 PROFINET Technical data Vibration- and shock- Vibration sinusoidal, in accordance with IEC 60068-2-6 resistance • 2 to 8.4 Hz, 3.5 mm peak • 8.4 to 2 000 Hz, 1 g peak Vibration broad-band random, according to IEC 60068-2-64 •...
Technical data Proline Promag H 300 PROFINET Conductivity ≥ 5 μS/cm for liquids in general. Pressure-temperature An overview of the pressure-temperature ratings for the process connections is ratings provided in the "Technical Information" document Pressure tightness Liner: PFA Nominal diameter...
Page 202
Technical data Proline Promag H 300 PROFINET Order code for "Housing", option A "Aluminum, coated" The various cable entries are suitable for hazardous and non-hazardous areas. Cable entry/cable gland Material Non-Ex: plastic Coupling M20 × 1.5 Z2, D2, Ex d/de: brass with plastic Adapter for cable entry with internal thread G ½"...
Technical data Proline Promag H 300 PROFINET 16.11 Human interface Languages Can be operated in the following languages: • Via local operation English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese, Japanese, Korean, Bahasa (Indonesian), Vietnamese, Czech, Swedish •...
Page 205
Proline Promag H 300 PROFINET Technical data Via remote display and operating module DKX001 The remote display and operating module DKX001 is available as an optional extra → 184. • The remote display and operating module DKX001 is only available for the following housing version: order code for "Housing": option A "Aluminum, coated"...
Page 206
Technical data Proline Promag H 300 PROFINET Supported operating tools Different operating tools can be used for local or remote access to the measuring device. Depending on the operating tool used, access is possible with different operating units and via a variety of interfaces.
Page 207
Proline Promag H 300 PROFINET Technical data • Flash firmware version for device firmware upgrade, for instance • Download driver for system integration • Visualize up to 1000 saved measured values (only available with the Extended HistoROM application package → 211) Web server special documentation →...
The device meets the legal requirements of the applicable EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. Ex approval The devices are certified for use in hazardous areas and the relevant safety instructions are provided in the separate "Safety Instructions"...
Page 209
• With the identification PED/G1/x (x = category) on the sensor nameplate, Directive Endress+Hauser confirms conformity with the "Essential Safety Requirements" specified in Appendix I of the Pressure Equipment Directive 2014/68/EU. • Devices not bearing this marking (PED) are designed and manufactured according to good engineering practice.
The application packages can be ordered with the device or subsequently from Endress+Hauser. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
For an overview of the scope of the associated Technical Documentation, refer to the following: • W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from nameplate • Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2D matrix code (QR code) on the nameplate Endress+Hauser...
Page 212
Technical data Proline Promag H 300 PROFINET Standard documentation Brief Operating Instructions Brief Operating Instructions for the sensor Measuring device Documentation code Proline Promag H KA01289D Brief Operating Instructions for transmitter Measuring device Documentation code Proline 300 KA01340D Technical Information...
Page 213
Proline Promag H 300 PROFINET Technical data Contents Documentation code INMETRO Ex ec XA01501D NEPSI Ex i XA01502D NEPSI Ex nA XA01503D Special Documentation Contents Documentation code Information on the Pressure Equipment Directive SD01614D Radio approvals for WLAN interface for A309/A310 display module...
Index Proline Promag H 300 PROFINET Index Degree of protection ..... 45, 198 Designated use ......9 About this document .
Page 215
Proline Promag H 300 PROFINET Index Editing view ....... 53 Input screen .
Page 216
Index Proline Promag H 300 PROFINET Measuring device Order code ......16, 17 Configuration .
Page 217
Proline Promag H 300 PROFINET Index Potential equalization ......38 Managing the device configuration ... 119 Power consumption .
Page 218