4-3-19 Hexadecimal, BCD Data Modification

Caution
!
1, 2, 3...
74
3. Press the Down Arrow Key and then the CHG Key.
4. At this point a new SV constant can be input or the SV constant can be
changed to a word address designation
a) To input a new SV constant, input the constant and press the WRITE
Key.
B
C
E
1
2
4
WRITE
b) To change to a word address designation, input the word address and
press the WRITE Key.
B
A
CH
SHIFT
1
0
WRITE
*
This operation can be used to increment and decrement an SV constant. It is
possible only when the SV has been entered as a constant.
1. Press the CLR Key to bring up the initial display.
2. Display the desired timer or counter.
TIM
3. Press the Down Arrow, CHG, and then the EXT Key.
CHG
The constant on the left is the old SV and the constant on the right will
become the new SV constant in step 5.
4. Press the Up and Down Arrow Keys to increment and decrement the con-
stant on the right. (In this case the SV is incremented once.)
5. Press the CLR Key twice to change the timer's SV to the new value.
CLR
This operation is used to change the BCD or hexadecimal value of a word
being monitored using the procedure described in 4-3-11 Bit, Digit, Word
Monitor. It is possible in MONITOR or PROGRAM mode only.
RUN
No
OK
Words SR 253 to SR 255 cannot be changed.
Check that there is no effect on equipment before changing the present values.
1. Monitor the status of the desired word according to the procedure described
in 4-3-11 Bit, Digit, Word Monitor. If two or more words are being monitored,
the desired word should be leftmost on the display.
(Word monitor)
00201DATA?
CHG
T001 #0123 #????
00201 TIM DATA
00201 TIM DATA
00201SRCH
SRCH
TIM
00201DATA ? U/D
EXT
T000 #0123 #0123
00201DATA ? U/D
T000 #0123 #0124
00201 TIM DATA
CLR