Gas Line Installation

After leveling, position the insert in the fireplace - holding it about six
inches out from its final location.
CAUTION: Specific hearth requirements apply (see Clearances
to Combustibles).
This appliance must be connected to the gas line in accordance with local
codes and/or the National Fuel Gas Code, ANSI Z223.1 (In Canada, the
current CAN/CGA B149.1 installation code). This appliance comes with
an 5" nipple, provided in the literature package. After connecting the gas
line, all joints in the line and connections at the valve should be checked
for leaks before final positioning of the unit. Conduct a gas leakage test
of the appliance piping and control system downstream of the shutoff
valve in the supply line to the appliance.

Gas Pressure Requirements

A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS
APPLIANCES IS IMPROPER GAS PRESSURE!
The most important item to check during the initial installation
and the first thing to check when operating problems occur is
gas pressure! This appliance will not function properly unless
the required gas pressure is supplied. See the tables on this
page for gas pressure requirements.
Gas Pressure Test Points
Manifold Gas Pressure Test Points - The outlet manifold test gauge
connection is provided on the valve stem (see Figure 19A).
Inlet Gas Pressure Test - The inlet line gas pressure test point is located
in the control compartment (see Figure 19B).
The control valves have a 3/8" (10 mm) NPT thread inlet and outlet side
of the valve.
If the pressure is not sufficient, make sure the gas supply line is large
enough, the supply regulator is properly adjusted and the total gas load
for the residence does not exceed the amount supplied.
Propane tanks are at pressures that will cause damage to valve com-
ponents. Verify that the tanks have step down regulators to reduce the
pressure to safe levels.
Check the taps for gas leaks with a gas leak test solution (retighten if
necessary).
Inlet Gas Supply Pressure
Fuel
Natural Gas
5" WC (1.25 kPa)
Propane
11.0" WC (2.74 kPa)
Manifold Gas Supply Pressure
Fuel
Pressure - High
Natural Gas
3.5" WC (0.87 kPa)
Propane
10.0" WC (2.49 kPa)
20
Minimum
Maximum
10.5" WC (2.61 kPa)
13.0" WC (3.23 kPa)
Pressure - Low
1.2" WC (0.30 kPa)
3.2" WC (0.80 kPa)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
The appliance must be isolated from the gas supply piping system
by closing its equipment shutoff valve during any pressure testing of
the gas supply piping system at test pressures equal to or less than
1/2 psig (3.5 kPa).
The appliance and its appliance main gas valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).
Ecoflow
Figure 19A - MANIFOLD Outlet Gas Pressure Test Point
Some parts have been removed for clarity
Testing Inlet Gas Pressure
(Qualified Technicians
Only):
1. Turn off gas shutoff
valve and electrical.
2. Remove 1/8" plug
(shown in diagram
below).
3. Install an 1/8" nipple in
place of plug.
4. Connect manometer to
nipple, using an 1/8"
NPT air hose nipple/
fitting.
5. Turn on shutoff valve
and check for proper
inlet gas pressure.
6. Reverse steps 1-5.
Figure 19B - INLET Line Gas Pressure Test Point

LP and Natural Gas Supplies

This appliance is equipped from the factory for use with natural gas only
as specified on the Safety / Listing label attached to the appliance. This
appliance can only be operated using propane gas (LP) if a certified fuel
conversion kit provided by IHP is installed by a qualified service technician.
Also check the orifice size on the label which is located in the control
compartment. It must be the correct size for the fuel and altitude.
Do not run propane tank dry. Running the tank dry may cause a
hazardous condition due to pressure drop in empty tank.
Solid fuel is NOT to be used with this appliance.
Outlet Pressure
Test Point
1/8" Inlet gas pressure 'test point' plug
(in control compartment)