 End Conditions
If either of the following conditions are satisfied, the muting state is released.
•Muting input 1 or 2 turns OFF at T3 or later (0.1s or later).
•The muting continuation time exceeds the muting time limit of T2 (60s).
ON
Muting input 1
OFF
ON
Muting input 2
OFF
Enabled
Muting state
Disabled
Muting lamp
Blinking
(external indicator)
OFF
F3SJ Unblocked
Unblocked
/Blocked
Blocked
ON
Safety output
OFF
*1 The value is applied to a single sensor. Values for connected sensors are:
# of connections
Single
0.15
2 connected
0.26
3 connected
0.29
• T1min: Muting input time limit (minimum value)
This is set to 0.03 sec., the minimum value for the input time difference between muting input 1 and 2.
A muting error occurs when the input time difference between muting input 1 and 2 is less than this
value.
•T1max: Muting input time limit (maximum value)
This is set to 3 sec., the maximum value for the input time difference between muting input 1 and 2.
•T2: Muting time limit
This is set to 60 sec., the muting function continuation time. When this muting state exceeds this time,
muting is released.
•T3: Muting input time with allowable waveform cracks
This is the maximum value for the waveform cracks allowed for muting input 1 and 2 when muting is
in effect. It is set to 0.1 sec.
Muting state can be released if a sensor transitions to lockout as well.
T3(0.1s) max.
T1min to T1max
0.15s max. *1
*1 Value (s)
System Configuration and Functions
T3(0.1s) max.
T2 max.
E
F3SJ-A
27
User's Manual