Omron F3SJ-A P 01TS Series User Manual page 36

Safety light curtain
Hide thumbs Also See for F3SJ-A P 01TS Series:
Table of Contents

Advertisement

System Configuration and Functions
 Wiring When External Device Monitoring Function Is Not Used
The external device monitoring function is disabled by connecting auxiliary output 1 and external
device monitoring input as shown below.
: External test switch (connect to 24V if a switch is not required)
S1
: Lockout reset switch (connect to 24V if a switch is not required)
S2
: Relay or other device that controls hazardous parts of the machine
K1, K2
: Load or PLC, etc. (for monitoring)
K3
*1 Use a switch for micro loads (Input specifications: 24V, 1.0mA or less)
*2 F3SJ can operate even if K3 is not connected. If K3 is not required, connect auxiliary output 1 to external device
monitoring input only.
Test input logic can be reversed by attaching a test input logic switching cap F39-CN7 to an emitter.
F3SJ-A
18
User's Manual
(Grey) Communication line (+)
(Pink)
Communication line (-)
S1
S2
*1
*1
K3
K1
K2
*2
+24V DC
Power
supply
0V