Eaton 93E MK2 Installation And Operation Manual page 32

Ups 10-40 kva 380/400/415v
Table of Contents

Advertisement

1.
If not already accomplished, use a forklift or pallet jack to move the UPS cabinet to the
installation area, or as close as possible, before unloading from the pallet. Insert the forklift or
pallet jack forks between the supports on the bottom of the pallet (see Figure 3-4 for the UPS
cabinet center of gravity measurements).
2.
Attach the ramp to the front of the pallet
3.
Remove four bolts securing the front shipping bracket to the cabinet and four bolts securing
the bracket to the pallet (see Figure 4-1). If installing the cabinet permanently, retain the
shipping bracket and securing hardware for later use.
4.
If the leveling feet are not fully retracted, turn the leveling feet until they are retracted.
5.
Remove four bolts securing the rear shipping bracket to the cabinet and four bolts securing
the bracket to the pallet (see Figure 4-1). If installing the cabinet permanently, retain the
shipping bracket and securing hardware for later use.
Do not stand directly in front of the pallet while unloading the cabinet. If unloading instructions are
not closely followed, the cabinet may cause serious injury.
6.
Slowly roll the cabinet toward the front of the pallet. Continue rolling the cabinet down the
ramp until the cabinet is clear of the ramp (see Figure 4-3).
7 .
Roll the cabinet to the final installation location.
8.
If installing the cabinet permanently, retain the shipping brackets and hardware; otherwise,
recycle the pallet, ramp, and shipping brackets in a responsible manner.
9.
Secure the UPS cabinet in position by lowering the leveling feet until the cabinet is not
resting on the casters and the cabinet is level.
10. If permanently mounting the system, proceed to Step 11;
11. Using the retained hardware, reinstall the shipping brackets removed in Step 2 and Step 5 to
the front and rear of the UPS cabinet with the angle facing outward (see Figure 4-1).
12. Secure the cabinet to the floor with customer-supplied hardware.
22
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation
WARNING

Advertisement

Table of Contents
loading

This manual is also suitable for:

93e

Table of Contents