UPS Installation Plan and Unpacking
Rated battery voltage/current is calculated at 2 volts per cell.
The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of
nominal battery voltage at rated battery current. If the conductors used for battery input from the battery cabinets to
the UPS are those provided by the UPS manufacturer, and the UPS and battery cabinets are manufactured by the
same supplier, then it is acceptable, even though they do not meet the above minimum conductor sizes.