6.4.2 Starting the Parallel UPS in Bypass Mode

If the inverter output of the parallel UPS is not available and the critical load needs to be energized:
In Bypass mode, the critical load is not protected from commercial power
interruptions and abnormalities.
1.
Unfasten the front door by lifting the latch from the bottom and turning to the right
(counterclockwise) and swing the door open (Figure 6-1).
2.
Verify that all input breaker are open.
3.
Verify that the Maintenance bypass switches are open.
4.
Close all Module Output Breakers (MOBs).
5.
Close all UPS input feeder circuit breakers.
6.
If the UPSs are wired for dual input, close all of the UPS Bypass input feeder circuit breakers.
7 .
Close all input breakers.
8.
If the UPSs are wired for dual input, close all of the bypass input switches.
9.
Make sure MBS cover is installed.
10. Close the door and secure the latch.
11. Close the external battery breakers.
11. Observe the UPS control panel display becoming active, indicating logic power.
12. Verify no alarms are active.
13. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
14. If not already selected, select UPS on the System Control screen.
15. On the UPS System Control screen, select the LOAD OFF
RETURN
pushbutton.
The critical load is immediately supplied by the bypass source, in Bypass mode from
all UPSs. The BYPASS status indicator is illuminated.
68
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation