Table 3-8. Recommended Bypass And Output Circuit Breaker Ratings; Table 3-9. Recommended Dc Input Circuit Breaker Rating - Eaton 93E Operation Manual

300/400 kva (380/400/415v)
Table of Contents

Advertisement

The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load shown in Table 3-5. The recommended line-to-line load unbalance is 50% or less.
With non-linear load, neutral current may reach 1.7 times of phase current.4 pole breaker rating shall be
sufficient in this case considering the neutral current.
Readily accessbible disconnect devices (Bypass and output overcurrent protection and bypass and output
disconnect switches) are to be supplied by the customer. Table 3-8 lists the recommended rating for bypass
and output circuit breakers.

Table 3-8. Recommended Bypass and Output Circuit Breaker Ratings

UPS Model
Eaton 93E-400/300
Eaton 93E-400/400
There is no DC disconnect device within the UPS. A battery disconnect switch is recommended, And may be
required by local codes when batteries are remotely located. The battery disconnect breaker should be installed
between the battery and the UPS
External DC input overcurrent protection and disconnect switch for the remote battery location is to be
provided by the user. Table 3-9 lists the maximum rating for continuous-duty rated circuit breakers satisfying the
criteria for both.

Table 3-9. Recommended DC input circuit breaker rating

UPS Model
Eaton 93E-400/300
Eaton 93E-400/400
Battery voltage is computed at 2 volts per cell. Rated battery current is computed at 2 volts per cell. The battery
wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC
voltage at rated battery current. If the conductors used for DC input from the battery cabinets to the UPS are
those provided by the UPS manufacturer, and the UPS and battery cabinets are manufactured by the same
supplier, then it is acceptable if they do not meet the noted minimum conductor sizes.
Circuit Breaker Rating
Load Derating
80% Derated
100% Rating
80% Derated
100% Rating
Circuit Breaker Rating
Load Derating
80% Derated
100% Rating
80% Derated
100% Rating
Eaton 93E UPS (300/400 kVA, 380/400/415V) Installation and Operation Manual
UPS Installation Plan and Unpacking
400V
541A
433A
721A
577A
Rated battery voltage (480V, 40 sections)
772A
618A
1030A
824A