Connect Signals - National Instruments SCXI-1166 Installation Manual

Hide thumbs Also See for SCXI-1166:
Table of Contents

Advertisement

3. Connect Signals

© National Instruments Corporation
To connect signals to the terminal block, complete the following steps:
1.
Prepare the signal wire by stripping the insulation no more than
3/16 of an inch.
2.
Gently pry the terminal block top cover off with a flathead screwdriver.
3.
Loosen the two 10-32 × 3/4 inch screws on the strain-relief bar, leaving
plenty of space for the signal cables.
4.
Pull the signal cables at least one foot through the strain-relief opening
shown in Figure 1.
5.
Connect the safety earth ground to the safety ground lug.
6.
Connect the wires to the terminals by inserting the stripped end of the
wire into the terminal. Secure the connection by tightening the screw
for each terminal. When connecting the signals, refer to the connection
diagram in Figure 2.
7.
Tighten the two 10-32 × 3/4 inch screws on the strain-relief bar, leaving
enough space for the signal wires.
8.
Snap the top cover onto the base.
3
NI SCXI-1366 Installation Guide

Advertisement

Table of Contents
loading

Table of Contents