Piping installation
8.1.5 To check the water volume: Examples
8.2 Connecting water piping
8.2.1 About connecting the water piping
Installer reference guide
78
a Schrader valve
Example 1
The outdoor unit is installed 5 m below the highest point in the water circuit. The
total water volume in the water circuit is 100 l.
No actions or adjustments are required.
Example 2
The outdoor unit is installed at the highest point in the water circuit. The total
water volume in the water circuit is 250 l.
Actions:
▪
Because the total water volume (250 l) is more than the default water volume
(185 l), the pre-pressure must be decreased.
▪
The required pre-pressure is:
Pg = (0.3+(H/10)) bar = (0.3+(0/10)) bar = 0.3 bar
▪
The corresponding maximum water volume at 0.3 bar is 270 l. (See the graph in
"Maximum water
volume" [
▪
Because 250 l is lower than 270 l, the expansion vessel is appropriate for the
installation.
Before connecting the water piping
Make sure the outdoor unit is mounted.
4
76]).
EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05