7.1.2 Additional installation site requirements of the outdoor unit in cold climates
EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
In areas with low ambient temperatures and high humidity, or in areas with heavy
snowfall, remove the suction grille to ensure proper operation.
Non-exhaustive list of areas: Austria, Czech Republic, Denmark, Estonia, Finland,
Germany, Hungary, Latvia, Lithuania, Norway, Poland, Romania, Serbia, Slovakia,
Sweden, ...
1 Remove the screws holding the suction grille.
2 Remove the suction grille, and dispose of it.
3 Reattach the screws to the unit.
4×
1
3
a Suction grille
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
c
a Snow cover or shed
b Pedestal
c Prevailing wind direction
d Air outlet
In any case, provide at least 300 mm of free space below the unit. Additionally,
make sure the unit is positioned at least 100 mm above the maximum expected
level of snow. See
"7.2 Mounting the outdoor
2
c
a
b
4
unit" [
64] for more details.
7
Unit installation
|
a
Installer reference guide
63