Service manual
Daikin Altherma 3 M

Advertisement

Table of Contents
loading

Summary of Contents for Daikin EBLA04E V Series

  • Page 1 Service manual Daikin Altherma 3 M EBLA04E▲V▼ EBLA06E▲V▼ EBLA08E▲V▼ EDLA04E▲V▼ EDLA06E▲V▼ EDLA08E▲V▼ ▲= A, B, C, …, Z ▼= , , 1, 2, 3, …, 9 draft – 31/05/2022 15:53...
  • Page 2 The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein.
  • Page 3 Version log Version log Version code Description Date ESIE22-09 Document release May 2022 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 4: Table Of Contents

    H1-00 – External temperature sensor problem .................... 54 3.3.51 H3-00 – Outdoor unit: Malfunction of high pressure switch ................ 55 3.3.52 H5-00 – Malfunction of compressor overload protection ................55 Service manual EBLA04~08E + EDLA04~08E Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 5 Built-in backup heater ............................ 116 4.3.2 Backup heater kit............................125 Backup heater thermal protector........................... 134 4.4.1 Built-in backup heater ............................ 134 4.4.2 Backup heater kit............................137 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 6 Water pump ..................................245 4.23.1 Checking procedures ............................245 4.23.2 Repair procedures ............................248 5 Third party components Electrical circuit................................254 5.1.1 Checking procedures ............................254 Service manual EBLA04~08E + EDLA04~08E Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 7 Component overview: Single phase without backup heater ................ 301 7.4.3 Component overview: Backup heater kit ...................... 303 Field information report ..............................304 Service tools ..................................307 Field settings ................................... 308 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 8: Safety Precautions

    WARNING: FLAMMABLE MATERIAL CAUTION Indicates a situation that could result in minor or moderate injury. NOTICE Indicates a situation that could result in equipment or property damage. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 9: Dangers

    Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. ONLY use accessories, optional equipment and spare parts made or approved by Daikin. WARNING Do NOT apply any permanent inductive or capacitance loads to the circuit without ensuring that this will NOT exceed the permissible voltage and current permitted for the equipment in use.
  • Page 10 WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation). WARNING Make sure the work site environment is clean and safe to work in. Beware of spilled fluids, like water, oil or other substances.
  • Page 11 HFC refrigerant because there is no chlorine component in the refrigerant. In case of R32 (HFC) refrigerant, any flame in contact with (leaking) refrigerant is extremely dangerous. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 12 After finishing the electrical work, confirm that each electrical component and terminal inside the electrical components box is connected securely. ▪ Make sure all covers are closed before starting up the unit. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 13 WARNING All maintenance staff and others working in the local area MUST be instructed on the nature of work being carried out. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 14 During the refrigerant recovery, confirm that the crankcase heater of the compressor body is energized to accelerate this process. When oil is drained from a system, it MUST be carried out safely. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 15: Cautions

    Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard. NOTICE Make sure the field piping and connections are NOT subjected to stress. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 16: General Operation

    Cooling mode The compressor capacity step is defined by the evaporation temperature, which is calculated through the low pressure sensor read-out. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 17 Polypropylene hot water tank domestic hot EKHWS(U) water tank EKHWP Floorstanding heat Wall mounted heat pump convector pump convector FWXV FWXT Concealed heat pump convector FWXM EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 18: Troubleshooting

    Conditions: The user permission level is set to advanced end user. 1 Go to [8.2]: Information > Malfunction history. You see a list of the most recent malfunctions. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 19: Error Based Troubleshooting

    "4.12 Hydro PCB" [  175]. Possible cause: Faulty hydro PCB. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 20: 04 - Water Flow Problem During Domestic Hot Water Production

    "4.12 Hydro PCB" [  175]. Possible cause: Faulty hydro PCB. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 21: 05 - Water Flow Problem During Heating/Sampling

    "4.12 Hydro PCB" [  175]. Possible cause: Faulty hydro PCB. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 22: 06 - Water Flow During Cooling/Defrost

     116]. Possible cause: Faulty backup heater. 11 If installed, perform a check of the booster heater. See "4.5  Booster heater" [  142]. Possible cause: Faulty booster heater. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 23: 07 - Water Flow Problem. Pump De-Blocking Active

    "4.12 Hydro PCB" [  175]. Possible cause: Faulty hydro PCB. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 24: Inlet Water Thermistor Abnormality

    3.3.9 81-01 – Mixed water thermistor abnormality Trigger Effect Reset Outlet water thermistor Unit will not stop Automatic reset. bizone input is out of operating. range. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 25: Outlet Water Temperature Thermistor Abnormality

    3 times, with interface. less than 30 minutes between each warning. To solve the error code INFORMATION It is recommended to perform the checks in the listed order. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 26: Heat Exchanger Frozen

    ≤0°C during space heating or domestic hot water. To solve the error code INFORMATION It is recommended to perform the checks in the listed order. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 27: Heat Exchanger Frozen

    <5°C or 1.5°C (glycol) for 5 seconds OR saturated evaporation temperature (pressure sensor) <−11°C for 5 minutes from start of cooling. Occurs after 1 automatic reset of error code 89-06. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 28: Heat Exchanger Freeze-Up Protection Activated During Cooling (Warning)

    <5°C or 1.5°C (glycol) for 5 seconds OR saturated evaporation temperature (pressure sensor) <−11°C for 5 minutes from start of cooling. At second occurrence, error 89‑05 is triggered. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 29: 00 - Abnormal Increase Outlet Water Temperature (Domestic Hot Water)

    1 Check the water flow. See "5.3 Water circuit" [  265]. Possible cause: Water flow is too low. 2 Perform a check of the outlet water after backup heater thermistor. See "4.19 Thermistors" [  217]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 30: 00 - Abnormal Increase Outlet Water Temperature

     116]. Possible cause: Faulty backup heater contactor(s). INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 31: 01 - Overheating Mixed Water Circuit

    Possible cause: Faulty thermal protector or faulty switching temperature of thermal protector. 2 Perform a check of the bizone kit PCB. See documentation of the bizone kit. Possible cause: Faulty bizone kit PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 32: 03 - Overheating Water Circuit (Thermostat)

    1 Perform a check of the main PCB. See "4.14 Main PCB" [  184]. Possible cause: Faulty main PCB. 2 Check if the power supply is compliant with the regulations. See "5.1 Electrical circuit" [  254]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 33: A5-00 - Outdoor Unit: High Pressure Peak Cut / Freeze Protection Problem

    10 Check for the presence of non‑condensables and/or humidity in the refrigerant circuit. See "5.2 Refrigerant circuit" [  256]. Possible cause: Non‑condensables and/or humidity in the refrigerant circuit. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 34: Backup Heater Overheated

    "4.12 Hydro PCB" [  175]. Possible cause: Faulty hydro PCB. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 35: Booster Heater Overheated

    ▪ Backup heater NOT allowed. 3 Check the domestic hot water tank and booster heater related settings. See "4.20 User interface" [  234]. Possible cause: Faulty booster heater settings. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 36: Too Long Domestic Hot Water Heat-Up Time Required

    Possible cause: Domestic hot water consumption too large. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 37: C0-00 - Flow Sensor Malfunction

    "5.3 Water circuit" [  265]. Possible cause: Water pressure is too low. 2 Check the water flow. See "5.3 Water circuit" [  265]. Possible cause: Water flow is too low. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 38: C0-02 - Flow Switch Malfunction

    "4.12 Hydro PCB" [  175]. Possible cause: Faulty hydro PCB. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 39: C4-00 - Heat Exchanger Temperature Sensor Problem

    "4.19 Thermistors" [  217]. Possible cause: Faulty refrigerant liquid thermistor. 4 Perform a check of the hydro PCB. See "4.12 Hydro PCB" [  175]. Possible cause: Faulty hydro PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 40: Room Temperature Sensor Problem

    It is recommended to perform the checks in the listed order. 1 Perform a check of the main PCB. See "4.14 Main PCB" [  184]. Possible cause: Faulty main PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 41: E2-00 - Leakage Current Detection Error

    Possible cause: Faulty compressor or miswiring of the compressor power supply cable. 2 Perform a check of the main PCB. See "4.14 Main PCB" [  184]. Possible cause: Faulty main PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 42: E3-00 - Outdoor Unit: Actuation Of High Pressure Switch

    Possible cause: Clogged refrigerant circuit. 8 Perform a check of the outdoor unit fan motor. See "4.15  Outdoor unit fan motor" [  197]. Possible cause: Faulty outdoor unit fan motor. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 43: E3-24 - High Pressure Switch Abnormality

     197]. Possible cause: Faulty outdoor unit fan motor. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 44: E4-00 - Abnormal Suction Pressure

    "4.14 Main PCB" [  184]. Possible cause: Faulty main PCB. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 45: E5-00 - Outdoor Unit: Overheat Of Inverter Compressor Motor

    "5.2 Refrigerant circuit" [  256]. Possible cause: Clogged refrigerant circuit. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 46: E6-00 - Outdoor Unit: Compressor Startup Defect

    "4.9 Expansion valve" [  162]. Possible cause: Faulty expansion valve. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 47: E7-00 - Outdoor Unit: Malfunction Of Outdoor Unit Fan Motor

    3 Perform a check of the main PCB. See "4.14 Main PCB" [  184]. Possible cause: Faulty main PCB. 4 Check if the power supply is compliant with the regulations. See "5.1 Electrical circuit" [  254]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 48: E9-00 - Malfunction Of Electronic Expansion Valve

    7 Perform a check of the main PCB. See "4.14 Main PCB" [  184]. Possible cause: Faulty main PCB. 8 Check if the power supply is compliant with the regulations. See "5.1 Electrical circuit" [  254]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 49: Outdoor Unit: Cool/Heat Switchover Problem

    Possible cause: Closed stop valve in the refrigerant circuit. 7 Check if the refrigerant circuit is clogged. See "5.2 Refrigerant circuit" [  256]. Possible cause: Clogged refrigerant circuit. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 50: Abnormal Increase Tank Temperature

    The water in the heating system and the tank is too cold to perform defrost operation, so the tank needs to be preheated electrically. Wait until preheating operation is done. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 51: F3-00 - Outdoor Unit: Malfunction Of Discharge Pipe Temperature

    "4.19 Thermistors" [  217]. Possible cause: Faulty refrigerant side thermistor(s). INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 52: F6-00 - Outdoor Unit: Abnormal High Pressure In Cooling

    3.3.48 FA-00 – Outdoor unit: Abnormal high pressure, actuation of high pressure switch Trigger Effect Reset Outdoor heat exchanger Unit will NOT stop Automatic reset when thermistor measures a operating. temperature drops. too high temperature. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 53: H0-00 - Outdoor Unit: Voltage/Current Sensor Problem

    3.3.49 H0-00 – Outdoor unit: Voltage/current sensor problem Trigger Effect Reset Compressor voltage (DC) Unit will stop operating. Manual reset via user is out of range before interface. start‑up. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 54: H1-00 - External Temperature Sensor Problem

    Possible cause: Faulty external indoor or outdoor ambient thermistor. 2 Perform a check of the hydro PCB. See "4.12 Hydro PCB" [  175]. Possible cause: Faulty hydro PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 55: H3-00 - Outdoor Unit: Malfunction Of High Pressure Switch

    Possible cause: Closed stop valve in the refrigerant circuit. 2 Check if the refrigerant circuit is clogged. See "5.2 Refrigerant circuit" [  256]. Possible cause: Clogged refrigerant circuit. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 56: H6-00 - Outdoor Unit: Malfunction Of Position Detection Sensor

    3 Check that all stop valves of the refrigerant circuit are open. See "5.2 Refrigerant circuit" [  256]. Possible cause: Closed stop valve in the refrigerant circuit. 4 Check if the refrigerant circuit is clogged. See "5.2 Refrigerant circuit" [  256]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 57: H8-00 - Outdoor Unit: Malfunction Of Compressor Input System

    3 Perform a check of the reactor. See "4.17 Reactor" [  210]. Possible cause: Faulty reactor. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 58: H9-00 - Outdoor Unit: Malfunction Of Outdoor Air Thermistor

    3.3.57 HJ-10 – Water pressure sensor abnormality Trigger Effect Reset Water pressure input is Unit will NOT stop Automatic reset when out of range. operating. water pressure is within range. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 59: J3-00 - Outdoor Unit: Malfunction Of Discharge Pipe Thermistor

    3.3.59 J6-00 – Outdoor unit: Malfunction of heat exchanger thermistor Trigger Effect Reset Outdoor heat exchanger Unit will stop operating. Manual reset via user thermistor input is out of interface. range. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 60: J8-00 - Malfunction Of Refrigerant Liquid Thermistor

    3.3.61 JA-00 – Malfunction of high pressure sensor Trigger Effect Reset Refrigerant pressure Unit will stop operating. Manual reset via user sensor detects a value out interface. of range (>4.5 MPa or <– 0.05 MPa). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 61: Refrigerant Pressure Sensor Abnormality

    Manual reset via user detects current/voltage interface. errors. Power reset. To solve the error code INFORMATION It is recommended to perform the checks in the listed order. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 62: L3-00 - Outdoor Unit: Electrical Box Temperature Rise Problem

    4 Clean the outdoor heat exchanger. See "6 Maintenance" [  275]. Possible cause: Dirty outdoor heat exchanger. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 63: L4-00 - Outdoor Unit: Malfunction Of Inverter Radiating Fin Temperature Rise

    Reset An output overcurrent is Unit will stop operating. Manual reset via user detected by checking the interface. current that flows in the inverter DC section. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 64 Possible cause: Thermal interface grease NOT applied properly on the heat sink. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 65: L8-00 - Malfunction Triggered By A Thermal Protection In The Main Pcb

    It is recommended to perform the checks in the listed order. 1 Perform a check of the compressor. See "4.7 Compressor" [  148]. Possible cause: Faulty compressor or miswiring of the compressor power supply cable. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 66: Malfunction In Communication System Of Outdoor Unit

     197]. Possible cause: Faulty outdoor unit fan motor. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 67: P1-00 - Open Phase Power Supply Imbalance

    3.3.72 P4-00 – Outdoor unit: Malfunction of radiating fin temperature sensor Trigger Effect Reset Radiating fin thermistor Unit will stop operating. Manual reset via user input is out of range. interface. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 68: Capacity Setting Mismatch

    Possible cause: Faulty refrigerant side thermistor(s). 2 Perform a check of the refrigerant pressure sensor. See "4.18  Refrigerant pressure sensor" [  212]. Possible cause: Faulty refrigerant pressure sensor. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 69: U1-00 - Malfunction By Reverse Phase/Open Phase

    ±4%), ▪ Power drop, ▪ Short circuit. 2 Perform a check of the main PCB. See "4.14 Main PCB" [  184]. Possible cause: Faulty main PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 70: U2-00 - Outdoor Unit: Defect Of Power Supply Voltage

    3.3.77 U3-00 – Under floor heating screed dry out function not completed correctly Trigger Effect Reset Under floor heating Unit will stop operating. Manual reset via user screed dry-out is interface. interrupted. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 71: U4-00 - Indoor/Outdoor Unit Communication Problem

    Possible cause: Faulty hydro PCB. Prerequisite: Stop the unit operation via the user interface. Prerequisite: Turn OFF the respective circuit breaker. 6 Wait until the rectifier voltage is below 10 V DC. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 72: U5-00 - User Interface Communication Problem

    ±4%), ▪ Power drop, ▪ Short circuit. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 73: U7-00 - Outdoor Unit: Transmission Malfunction Between Main Microcomputer - Inverter Microcomputer

    2 Check the communication wiring between the remote controller and the unit. "4.20 User interface" [  234]. Possible cause: Faulty wiring between the remote controller and the unit. 3 Perform a check of the room thermistor: EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 74: U8-03 - No Connection With Room Thermostat

    Possible cause: Faulty wiring between the remote controller and the unit. 4 Perform a check of the hydro PCB. See "4.12 Hydro PCB" [  175]. Possible cause: Faulty hydro PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 75: U8-04 - Unknown Usb Device

    CANNOT be found on the USB/SDcard. CAUTION Always safely remove and eject media. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 76: U8-06 - Bizone Kit Canopen Communication Error

    3 Perform a check of the hydro PCB. See "4.12 Hydro PCB" [  175]. Possible cause: Faulty hydro PCB. 4 Check if the power supply is compliant with the regulations. See "5.1 Electrical circuit" [  254]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 77: U8-09 - User Interface Software Version / Indoor Unit Compatibility Error

    It is recommended to perform the checks in the listed order. 1 Check that the AP mode is active (= WLAN adapter active as access point). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 78: Indoor Unit, Outdoor Unit Mismatching Problem

    It is recommended to perform the checks in the listed order. 1 Check for improper combination of the indoor unit and the water tank. See the combination table in the Databook for more information. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 79: Reversed Piping Or Bad Communication Wiring Detection

     281]. Possible cause: Piping and/or wiring mismatch. INFORMATION If all procedures listed above have been performed and the problem is still present, contact the helpdesk. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 80: Symptom Based Troubleshooting

    Adjust water pressure if checked during filling, required (±2 bar). ▪ Air was purged from the water circuit after filling, ▪ Leakage. ▪ Expansion vessel broken or not properly pre-adjusted. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 81 Check Repair Incorrect setting of pump Incorrect setting. Confirm setting [F‑0]. Adapt setting [F‑0] if operation mode required (factory setting: (continuous, sample, [F‑0]=1). request) (setting [F‑0D]). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 82: Tap Water Related

    Bad quality/contamination Check the water quality Assure that quality of of supply water. of supply water. (odour/contamination) at entering water is OK. cold domestic water inlet. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 83: Symptom: User Interface Is Failure Or Frozen Screen

    Replace safety valve. Safety valve leaking. Component failure. Check safety valve. Replace safety valve. Leakage of drain valve. Component failure. Check drain valve. Replace drain valve. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 84: Symptom: Water Flow Or Volume Too Low

    Correct the U, V, W wiring. incorrectly connected to repair. wiring is correctly compressor. connected. See "7.2 Wiring diagram" [  281] for an indication how to connect correctly. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 85 ▪ Check refrigerant refrigerant circuit. (with contact circuit for blockages. thermometer) before the compressor and comparing with the saturated evaporation temperature. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 86 Unit produces (loud) noise ▪ Refrigerant overcharge, Check refrigerant. After vacuum drying, or shakes. charge correct amount of ▪ Mixing refrigerant. refrigerant system, ▪ Refrigerant undercharge. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 87: Symptom: Abnormal Presence Of Ice

    Outdoor unit installation enough to defrost due to MUST be protected from too strong wind, snow, ... weather (wind, snow, ...). See installer reference guide for correct installation. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 88: Symptom: Domestic Hot Water Capacity Shortage

    Domestic hot water tank Check domestic hot water Replace domestic hot water tank thermistor. thermistor measures a tank thermistor. water tank thermistor. higher temperature than actual (component failure). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 89: Symptom: General Capacity Shortage

    ▪ Check refrigerant refrigerant circuit. (with contact thermometer) before the circuit for blockages. compressor and comparing with the saturated evaporation temperature. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 90 (cooling). Water filter blocked. Dirty water. ▪ Check water filter, ▪ Clean the water filter, ▪ Check water quality. ▪ Check the water quality. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 91 Check the flow sensor. Replace the flow sensor. flow measured higher than actual. 3‑way valve blocked. Component failure. Check the 3‑way valve. Replace the 3‑way valve. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 92: Symptom: Space Heating (Cooling) Capacity Shortage

    3‑way valve incorrectly Check the 3‑way valve. Correct the position of the switch correctly between mounted. 3‑way valve. space heating (cooling) connection and domestic hot water connection. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 93: Symptom: Inaccurate Temperature Control

    NOT representing room in case of room thermostat position to measure the accurate room temperature. control (setting [C‑07]=2). correct room temperature. temperature measurement. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 94: Symptom: Power Consumption Too High

    User set too high leaving Check leaving water Adapt leaving water temperature setpoint. water temperature setpoint. setpoint (e.g. <55°C will setpoint by schedule or reduce backup heater manual operation. operation). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 95 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 96: Symptom: System Does Not Start Or Operate

    [9‑0C], ▪ Setting 3: outlet water temperature control => Thermo on: outlet water temperature = setpoint. Thermo off: outlet water temperature –1,5°C. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 97 NOT match. NOT match. (see installer reference guide). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 98: Symptom: The Pump Is Blocked

    Note: Do NOT use excessive force. If you cannot deblock the rotor of the pump with this method, you will need to disassemble the pump and turn the rotor by hand. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 99: Components

    Result: The measured voltage MUST be 230 V AC. 7 Measure the voltage on connector X2M pin 13 and pin 12. Result: The measured voltage MUST be 0 V AC. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 100 4 The 3-way valve can be installed in accordance with one of the following four configurations. Water inlet and exit locations differ depending on the configuration used in your unit. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 101 Exit Temperature Domestic hot water Same as the 3-way valve inlet Space heating "Much" lower than the 3-way valve inlet EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 102: Repair Procedures

    4 Cut all tie straps that fix the 3‑way valve motor harness. 5 Pull the 3-way valve knob and remove it from the 3‑way valve motor. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 103 1 If applicable, remove the insulation that covers the 3‑way valve body. 2 Remove the 3‑way valve body from the water piping. 3 To install the 3‑way valve body, see "4.1.2 Repair procedures" [  102]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 104 3 When installing in accordance with configurations E3 or E4, open the valve motor cover by loosening the screw and change the jumper so as to change the rotation direction of the valve. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 105 5 Tighten the screw to fix the 3‑way valve motor to the 3‑way valve body. a 3‑way valve motor b Screw 6 Install the 3‑way valve knob on the 3‑way valve motor. a 3-way valve knob b 3-way valve motor EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 106 3 Space heating exit 2 Depending on the configuration used in your unit, put the 3‑way valve body axle (notch) in the correct position (see image below). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 107 5 Tighten the screw to fix the 3‑way valve motor to the 3‑way valve body. a Screw 6 Install the 3‑way valve knob on the 3‑way valve motor. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 108: 4-Way Valve

    The coil gets hot while energized. Wait for it to cool down. 2 Verify that the screw is firmly fixing the coil to the valve body. 3 Check if any damage or burst is present. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 109 Are the measured voltages correct? Action Perform a position check of the 4-way valve, see "4.2.1 Checking procedures" [  108]. Perform a check the main PCB, see "4.14 Main PCB" [  184]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 110 Is the measured voltage correct? Action Perform a position check of the 4-way valve, see "4.2.1 Checking procedures" [  108]. Perform a check the main PCB, see "4.14 Main PCB" [  184]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 111 "7.3 Piping diagram" [  297]). INFORMATION The flow through the 4-way valve is correct if the water temperature after the heat exchanger rises/drops when operating in Heating/Cooling mode. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 112 2 Check with a contact thermometer (or by touching) if the flow through the 4- way valve corresponds with the flow shown in the flow diagram of the specific operation mode. (See "7.3 Piping diagram" [  297]). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 113: Repair Procedures

    Prerequisite: If needed, remove any parts to create more space for the removal of the 4‑way valve coil. 1 Remove the screw and remove the 4‑way valve coil from the 4‑way valve body. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 114 4‑way valve pipe b 4‑way valve c Putty d Insulation 5 Stop the nitrogen supply when the piping has cooled down. 6 Remove the 4‑way valve. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 115 10 Add refrigerant refrigerant circuit, "5.2.2  Repair procedures" [  261]. To install the 4-way valve coil 1 Install the 4‑way valve coil on the 4‑way valve body. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 116: Backup Heater

    Prerequisite: Stop the unit operation via the user interface. Prerequisite: Turn OFF the respective circuit breaker. 1 Remove the required plate work, see "4.16 Plate work" [  202]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 117 To prevent damage to the unit, all circuit breakers MUST be opened before using a Megger. 2 Set the Megger voltage to 500 V AC. 3 Connect the Megger ground test lead directly to the backup heater ground wire. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 118 Replace the backup heater, see "Repair procedures" [  120]. Return to "Checking procedures" [  116] of the backup heater and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 119 The measured voltages MUST be 230 V AC ± 10% (contacts closed). a Backup heater contactor K1M Are the measured voltages of the Action backup heater contactor correct (contacts closed)? Continue with the next step. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 120  202]. 1 Drain water from the water circuit, see "5.3.2 Repair procedures" [  269]. 2 Cut the tie strap(s) and remove the insulation from the backup heater. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 121 Clip (lower backup heater pipe) b Clip (backup heater coupling) c Lower backup heater coupling d Backup heater e Bracket 9 Separate the upper and lower backup heater coupling. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 122 Lower backup heater coupling d Backup heater e Bracket INFORMATION Make sure that the back‑up heater pipe is fully inserted in the back‑up heater coupling. a Clip EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 123 4 Install the clips on the upper and lower backup heater pipe. 5 Connect the ground wire to the switch box using the screw. Tighten the screw. 6 Connect the backup heater connector X12Y. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 124 2 Connect the wiring to the correct backup heater contactor terminals. Is the problem solved? Action No further actions required. Return to "Checking procedures" [  116] of the backup heater and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 125: Backup Heater Kit

    K1M/3 K1M/5 53 Ω 53 Ω 106 Ω 106 Ω K2M/1 K5M/13 26.5 Ω 26.5 Ω K2M/3 53 Ω 53 Ω K2M/5 53 Ω 53 Ω K2M/3 K2M/5 53 Ω 53 Ω 53 Ω 53 Ω K1M/5 K2M/1 132.5 Ω 132.5 Ω EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 126 To perform an electrical check of the backup heater Prerequisite: First perform an insulation check of the backup heater, see "Checking procedures" [  125]. Prerequisite: Check the circuit breaker. Reset if it has tripped. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 127 To perform a check of the backup heater contactors 1 First perform an electrical check of the backup heater, see "Checking procedures" [  125]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 128 3 With the Actuator test run still active, activate backup heater: step 1. 4 Measure the voltage between the following terminals of the backup heater contactors. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 129 For backup heater option with 3~, 400 V, 6 kW or 9 kW backup heater: ▪ K1M: 1‑3, 3‑5, 1‑5 ▪ K2M: 1‑3, 3‑5, 1‑5 ▪ K5M: 1‑3, 3‑5, 1‑5, 1‑13 All measured voltages MUST be 0 V AC (contacts open). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 130 2 Unscrew and remove the air purge valve from the backup heater. Keep for reuse. 3 Cut the insulation that covers the upper backup heater coupling. 4 Open the insulation and remove the screw from the pipe clamp. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 131 9 Remove the clip from the lower backup heater coupling. a Clip b Lower backup heater coupling c Backup heater 10 Separate the lower backup heater coupling. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 132 Clip b Lower backup heater coupling c Backup heater INFORMATION Make sure that the back‑up heater pipe is fully inserted in the back‑up heater coupling. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 133 11 Install and restore all insulation. INFORMATION Take care NOT to damage the insulation during installation. 12 Open the valve (if equipped) of the water circuit towards the expansion vessel. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 134: Backup Heater Thermal Protector

    Prerequisite: Stop the unit operation via the user interface. Prerequisite: Turn OFF the respective circuit breaker. Prerequisite: Remove the required plate work, see "4.16 Plate work" [  202]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 135 82°C), measure the resistance between the backup heater thermal protector wires on terminal X7M: 5‑6. Result: The resistance MUST be 0  Ω (backup heater thermal protector contacts are closed). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 136 To install the backup heater thermal protector 1 Install the backup heater thermal protector and new gasket on the backup heater. INFORMATION Make sure the gasket is correctly installed. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 137: Backup Heater Kit

    1 If the backup heater thermal protector has tripped: ▪ Sufficiently cool the sensor (7 K) ▪ Press the red button to reset the backup heater thermal protector EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 138 Prerequisite: Stop the unit operation via the user interface. Prerequisite: Turn OFF the respective circuit breaker. 1 Remove the 2 screws from the backup heater thermal protector bracket. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 139 2 Remove the backup heater thermal protector sensor from the backup heater. 3 Guid the backup heater thermal protector sensor and wiring through the grommet inside the switch box. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 140 1 Route the backup heater thermal protector sensor and wiring through the grommet of the switch box. 2 Insert the backup heater thermal protector sensor in the backup heater. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 141 2 screws. Is the problem solved? Action No further actions required. Return to the troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 142: Booster Heater

    Action resistance correct? Return to "4.5.1 Checking procedures" [  142] of the booster heater and continue with the next procedure. Replace the booster heater, see "4.5.2 Repair procedures" [  146]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 143 5 Check the status in the Actuators menu of the user interface. This MUST be: ▪ Booster heater test = ON 6 Check if the field installed circuit breaker has tripped. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 144 4 Measure the voltage between the following terminals of the booster heater contactor. ▪ K3M: 1‑3 / 2‑4 The measured voltages MUST be 230 V AC ± 10% (contacts closed). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 145 ▪ 0 V AC when the contacts should be open. Is the measured operating voltage of Action the booster heater contactor correct? Replace the specific booster heater contactor(s), see "4.5.2 Repair procedures" [  146]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 146: Repair Procedures

    1 Disconnect the wiring from the booster heater contactor terminals. 2 Remove the screws and remove the booster heater contactor(s) from the switch box. 3 To install booster heater contactor(s), "4.5.2  Repair procedures" [  146]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 147: Booster Heater Thermal Protector

    "4.6.2 Repair procedures" [  147]. 4.6.2 Repair procedures To remove the booster heater thermal protector 1 For the correct procedure, see the installation manual of the water tank. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 148: Compressor

    A mechanical lock is present on the Action compressor? Replace the compressor, see "4.7.2 Repair procedures" [  153]. Perform an mechanical check of the compressor, see "4.7.1 Checking procedures" [  148]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 149 Compressor dampers are in a good Action condition? Perform an electrical check of the compressor, see "4.7.1 Checking procedures" [  148]. Replace the compressor and/or damaged dampers, see "4.7.2 Repair procedures" [  153]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 150 Note the position of the Faston connectors on the compressor wire terminals to allow correct connection during installation. U Wire terminal U V Wire terminal V W Wire terminal W EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 151 11 Wait for – or create condition to operate the compressor. 12 Once the compressor operates, measure the U-V-W inverter voltages. ALWAYS measure at the PCB side. Result: All measurements MUST be the same. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 152 3 Disconnect the Faston connectors from the compressor wire terminals U, V and W. INFORMATION Note the position of the Faston connectors on the compressor wire terminals to allow correct connection during installation. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 153: Repair Procedures

    Confirm the rectifier voltage is below 10  V  DC before proceeding, see "To prevent electrical hazards" [  254]. 2 Remove the cover of the compressor wire terminals. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 154 6 Wrap a wet rag around the components near the compressor pipes. Heat the brazing points of the compressor pipes using an oxygen acetylene torch and remove the refrigerant pipes from the compressor pipes using pliers. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 155 11 Install plugs or caps on the open pipe ends of the refrigerant piping to avoid dirt or impurities from entering the piping. 12 To install the compressor, see "4.7.2 Repair procedures" [  153]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 156 0.02 MPa. 8 Wrap a wet rag around the compressor pipes and any other components near the compressor and solder the compressor pipes to the refrigerant pipes. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 157 11 Connect the Faston connectors to the compressor wire terminals U, V and W U Wire terminal U V Wire terminal V W Wire terminal W 12 Install the cover of the compressor wire terminals. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 158: Compressor Thermal Protector

    Prerequisite: Turn OFF the respective circuit breaker. Prerequisite: Remove the required plate work, see "4.16 Plate work" [  202]. Prerequisite: Remove the compressor insulation. 1 Remove the cover of the compressor wire terminals. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 159 6 Measure the resistance on the compressor thermal protector. Result: The contact MUST be open (measured resistance = OL). 7 Let the compressor thermal protection cool down below 85°C (reset temperature is 85~105°C). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 160: Repair Procedures

    1 Remove the cover of the compressor wire terminals. a Compressor wire terminals cover 2 Remove the compressor thermal protector with bracket from the compressor housing. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 161 To install the compressor thermal protector 1 Install the compressor thermal protector on the compressor thermal protector bracket. a Compressor thermal protector b Compressor thermal protector bracket EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 162: Expansion Valve

    4.9 Expansion valve 4.9.1 Checking procedures INFORMATION It is recommended to perform the checks in the listed order. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 163 5 or to pin 6 of the expansion valve coil connector. Connections may differ according to the type of expansion valve. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 164 To perform an operation check of the expansion valve Prerequisite: First perform an electrical check of the expansion valve, see "4.9.1 Checking procedures" [  162]. 1 Turn ON the power of the unit. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 165 Component is OK. Return to the troubleshooting of the specific error and continue with the next step. Replace the expansion valve, see "4.9.2 Repair procedures" [  166]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 166: Repair Procedures

    Prerequisite: Recuperate the refrigerant from the refrigerant circuit, see "5.2.2 Repair procedures" [  261]. Prerequisite: If needed, remove any parts or insulation to create more space for the removal. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 167 6 Wrap a wet rag around the expansion valve body and any other components near the expansion valve and solder the expansion valve pipes to the refrigerant pipes. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 168 Make sure to install the expansion valve coil in the correct position (orientation). a Expansion valve coil b Metal bracket c Nipple d Notch e Expansion valve body EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 169: Flow Switch

    8 Go to Actuator test run via the user interface. 9 Activate the Pump. 10 Make sure to select high speed and check that the water flow is >15 L/min. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 170: Repair Procedures

    1 Install (screw) the flow switch on correct location on the piping and in the correct orientation (arrow pointing in the direction of the water flow). Ensure that the O-ring is correctly installed and NOT damaged. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 171: High Pressure Switch

    Prerequisite: Stop the unit operation via the user interface. Prerequisite: Turn OFF the respective circuit breaker. Prerequisite: Remove the required plate work, see "4.16 Plate work" [  202]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 172 9 Lower the pressure of the nitrogen in the refrigerant circuit just below reset pressure of the high pressure switch. 10 Measure the resistance between the Faston connections of the high pressure switch. Result: The switch MUST be closed. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 173: Repair Procedures

    High pressure switch b Faston connector c High pressure switch pipe 6 Stop the nitrogen supply when the piping has cooled down. 7 Remove the high pressure switch. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 174 "5.2.2  Repair procedures" [  261]. Is the problem solved? Action No further actions required. Return to the troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 175: Hydro Pcb

    Correct the wiring between the main power supply terminal and the hydro PCB, see "4.12.2 Repair procedures" [  178]. Adjust the power supply to the unit, see "5.1.2 Repair procedures" [  256]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 176 Action PCB installed? Return to "4.12.1 Checking procedures" [  175] of the hydro PCB and continue with the next procedure. Replace the hydro PCB, see "4.12.2 Repair procedures" [  178] EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 177 Blown fuse on the hydro PCB? Action Replace the blown fuse, see "4.12.2 Repair procedures" [  178] Return to "4.12.1 Checking procedures" [  175] of the hydro PCB and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 178: Repair Procedures

    2 Disconnect all connectors and the ground wire from the hydro PCB. 3 Carefully pull the hydro PCB and unlatch the PCB supports one by one using a small pliers. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 179 1 Install the hydro PCB in the correct location in the switch box. a PCB support b Hydro PCB 2 Connect all connectors and ground wire to the hydro PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 180 1 Install the fuse on the correct location on the PCB. CAUTION Make sure the fuse is plugged‑in correctly (contact with the fuse holder). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 181: Lan Adapter Pcb

    Indication of power to the ▪ flashing: normal adapter, and of normal operation. operation. ▪ flashing: operation. Replace the LAN adapter PCB, "4.13.2  Repair procedures" [  183]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 182 NO Smart Grid operation is possible. a LED 1: heartbeat b LED 2: LAN communication c LED 3: P1/P2 communication d LED 4: smart grid control active EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 183: Repair Procedures

    4.13.2 Repair procedures To remove the LAN adapter PCB 1 See installer reference guide of the LAN adapter PCB for correct procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 184: Main Pcb

    1 Turn ON the power of the unit. 2 Measure the voltage between the black and white wires. Result: The measured voltage MUST be 230 V AC. a HL1 b HN1 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 185 4 Tilt the switch box until the wiring connection on the power supply terminal is accessible. 5 Measure the power supply voltage between L‑N on switch box terminal X1M. Result: The measured voltage MUST be 230 V AC. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 186 (1 second ON/1 second OFF)? Return to "4.14.1 Checking procedures" [  184] of the main PCB and continue with the next procedure. Replace the main PCB, see "4.14.2 Repair procedures" [  193]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 187 Prerequisite: First perform all earlier main PCB checks, see "4.14.1  Checking procedures" [  184]. 1 Measure the continuity of the fuse. If no continuity is measured, the fuse has blown. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 188 1 Turn ON the power of the unit. 2 Measure the voltage on the rectifier voltage check terminals (+ and –) on the main PCB. Result: The measured voltage MUST be approximately 324 V DC. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 189 Confirm the rectifier voltage is below 10  V  DC before proceeding, see "To prevent electrical hazards" [  254]. 4 Check the diode module in reference with the image and the table below. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 190  254]. Power module IPM1 for compressor 1 Disconnect the compressor connector. 2 Check the power module IPM1 in reference with the image and the table below. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 191 Power module IPM2 for fan motor 1 Disconnect the fan motor connector from the main PCB. 2 Check the power module IPM2 in reference with the image and the table below. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 192 After all checking procedures listed above have been performed: Is the problem solved? Action No further actions required. Return to the troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 193: Repair Procedures

    4 Cut the tie straps to disconnect the compressor wiring harness (part connected to the PCB) from the switch box. a Compressor wiring b Power supply wires from X1M c Wire from X2M EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 194 10 Disconnect all other connectors from the main PCB. 11 Remove the screws from the main PCB. a Screw b Main PCB 12 Remove the main PCB from the switch box. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 195 Heat sink contact surface 2 Install the main PCB in the correct location on the switch box. 3 Install and tighten the screws to fix the main PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 196 The 2 screws at the hydro box side are reachable using a small ratchet ¼ inch and socket nr. 8 or wrench ¼ inch with a cardan joint. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 197: Outdoor Unit Fan Motor

    Action damaged? Replace the propeller fan blade assembly, see "4.15.2 Repair procedures" [  199]. Perform a mechanical check of the DC fan motor assembly, see "4.15.1 Checking procedures" [  197]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 198 8 Unplug the DC fan motor connector and measure the resistance between the pins 1-3, 1-5, and 3-5 of the DC fan motor connector. Result: All measurements MUST be 25.93~28.67 Ω. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 199: Repair Procedures

    2 Remove the nut that fixes the propeller fan blade assembly. a Nut b Propeller fan blade assembly 3 Pull and remove the propeller fan blade assembly from the DC fan motor assembly. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 200 To install the DC fan motor assembly 1 Install the DC fan motor assembly in the correct location. 2 Fix the DC fan motor assembly to the unit by tightening the screws. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 201 Do NOT install a damaged propeller fan blade assembly. 2 Install and tighten the nut to fix the propeller fan blade assembly. a Nut b Propeller fan blade assembly EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 202: Plate Work

    2 Loosen and remove the screws that fix the discharge grille. a Screw 3 Remove the discharge grille. 4.16.2 To open the outdoor unit DANGER: RISK OF ELECTROCUTION DANGER: RISK OF BURNING/SCALDING EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 203: To Remove The Top Plate

    Prerequisite: Remove the top plate and the discharge grille, see "4.16  Plate work" [  202]. 1 Remove the retainers from the hinges of the hydro switch box. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 204: To Rotate The Switch Box

    Prerequisite: The front plate has been removed. 1 Push down the clip of the switch box holder. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 205: To Remove The Compressor Sound Insulation

    4.16.7 To remove the drip proof cover Prerequisite: Remove the top plate, see "4.16 Plate work" [  202]. 1 Remove the drip proof cover from the top of the switch box. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 206: To Remove The Switch Box

    Switch box 2 Tilt the switch box until the wiring connection on the power supply terminal is accessible. 3 Disconnect the wiring from the switch box. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 207 8 Disconnect the connectors from the main PCB. 9 Disconnect the compressor harness connector. 10 Remove the switch box from the unit. 11 To install the switch box, see "4.16 Plate work" [  202]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 208: To Install The Switch Box

    When reconnecting a connector to the PCB, make sure to connect it on the correct location and do NOT apply force, as this may damage the connector or connector pins of the PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 209: To Close The Outdoor Unit

    Speed nut. Make sure the speed nut for the top screw is correctly attached to the service cover. 3.55 N . m 5× a Speed nut EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 210: Reactor

    5 Measure the resistance of the reactor using a low ohm multi meter. Result: The resistance MUST be as follows: Measuring points Resistance d‑e 29.6~44.4 mΩ 152~228 mΩ g‑h 15.2~22.8 mΩ 96~144 mΩ EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 211 "4.17.2 Repair procedures" [  212]. 6 Measure the inductance of the reactor using an LCR meter. Result: The inductance MUST be as follows: Measuring points Resistance d‑e 123.5~136.5 µH EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 212: Repair Procedures

    2 Connect a pressure gauge to the gas service port. Read the pressure. 3 Using the graphic below, determine the expected sensor output voltage based on the pressure obtained in the previous step. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 213 V (DC) Detected pressure MPa 0.01 0.15 0.29 0.42 0.56 0.70 0.84 0.98 1.11 1.25 1.39 1.53 1.67 1.80 1.94 2.08 2.22 2.36 2.49 2.63 2.77 2.91 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 214 7 Unplug the connector X60A and measure the voltage (power supply) between pins 3–4 on the hydro PCB. Result: The measured voltage MUST be +5 V DC. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 215: Repair Procedures

    It is ALSO possible to cut the component pipe(s) using a pipe cutter. Make sure to remove the remaining component pipe end(s) from the refrigerant pipes by heating the brazing point(s) of the component pipe(s) using an oxygen acetylene torch. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 216 "5.2.2  Repair procedures" [  261]. Is the problem solved? Action No further actions required. Return to the troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 217: Thermistors

    S90: 3‑4 exchanger thermistor Discharge pipe Main S90: 5‑6 thermistor Refrigerant Hydro X7A: 1‑2 liquid thermistor 4 Determine the thermistor resistance that matches the measured temperature. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 218 15.43 4.70 59.43 14.79 4.54 56.49 14.18 4.38 53.71 13.59 4.23 51.09 13.04 4.08 48.61 12.51 3.94 46.26 12.01 3.81 44.05 11.52 3.68 41.95 11.06 3.56 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 219 Replace the specific thermistor, see "Repair procedures" [  219]. Repair procedures To remove the thermistor Prerequisite: Stop the unit operation via the user interface. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 220 - Remove the thermistor from the thermistor holder. a Tie strap b Insulation c Thermistor wire d Clip e Thermistor f Thermistor holder 3 Cut all tie straps that fix the thermistor harness. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 221 ▪ For refrigerant piping thermistors: Pull the clip and install the thermistor in the specific thermistor holder. Make sure the clip is in the correct position (blocking the thermistor). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 222 5 Fix the insulation and the thermistor wire using new tie straps. Is the problem solved? Action No further actions required. Return to the troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 223: Water Side Thermistors

    Hydro X6A: 1‑2 For units after backup with built‑in heater backup thermistor heater: - For units with backup heater kit: ▪ X5M: 1‑2 ▪ X15M: 1‑2 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 224 2.91 –14 139.94 30.06 8.37 2.82 –13 132.28 28.70 8.05 2.72 –12 125.09 27.41 7.75 2.64 –11 118.34 26.18 7.46 2.55 –10 111.99 25.01 7.18 2.47 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 225 4.360 1.478 12.499 3.594 1.255 5 Disconnect the thermistor connector from the appropriate PCB and measure the resistance between the appropriate pins of the thermistor connector. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 226 Continue with the next step. 1 Disconnect the thermistor from the intermediate connector and measure the resistance of the thermistor (between the appropriate pins of the connector). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 227 1 Locate the thermistor that needs to be removed. 2 Cut the tie straps that fix the insulation and the thermistor wire. a Tie strap b Insulation EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 228 To install the thermistor 1 Pull the clip and install the thermistor in the specific thermistor holder. Make sure the clip is in the correct position (blocking the thermistor). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 229: Other Thermistors

    Checking procedures To perform a mechanical check of the external thermistor Prerequisite: Stop the unit operation via the user interface. Prerequisite: Turn OFF the respective circuit breaker. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 230 2.91 –14 139.94 30.06 8.37 2.82 –13 132.28 28.70 8.05 2.72 –12 125.09 27.41 7.75 2.64 –11 118.34 26.18 7.46 2.55 –10 111.99 25.01 7.18 2.47 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 231 If the measured resistance value matches the resistance determined through the measured temperature, but the temperature for the corresponding thermistor is NOT correct on the user interface display, replace the applicable PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 232 3 Determine the thermistor resistance that matches the measured temperature. Thermistor – Table A T °C kΩ T °C kΩ T °C kΩ T °C kΩ –20 197.81 39.96 10.63 3.44 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 233 Resistance at 20°C: 24.3 kΩ, Resistance at 25°C: 19.4 kΩ, ▪ Measure resistance between pin 1‑2: Measured resistance: 21.86 kΩ, ▪ Measured resistance value is inside the range. Thermistor passes the check. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 234: User Interface

    PCB. Result: The measured voltage MUST be 12 V DC. Does the user interface receive power? Action Check if the user interface functions correctly, see "4.20.1 Checking procedures" [  234]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 235 Action Replace the remote controller user interface, see "4.20.2 Repair procedures" [  236]. Correct the wiring between the remote controller and the unit PCB, see "7.2 Wiring diagram" [  281]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 236: Repair Procedures

    To remove the user interface 1 See relevant manual of the user interface (remote controller) for the correct procedure. 2 To install the user interface, see "4.20.2 Repair procedures" [  236]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 237: Water Flow Sensor

    6 Measure the water flow with a calibrated external flow meter. 7 Measure the frequency on connector X34A between pins 2‑3 (= flow sensor output signal) on the hydro PCB. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 238: Repair Procedures

    Prerequisite: Turn OFF the respective circuit breaker. Prerequisite: Remove the required plate work, see "4.16 Plate work" [  202]. 1 Disconnect the connector from the water flow sensor. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 239 5 Remove the 2 clips that fix the water flow sensor. 6 Remove the water flow sensor. 7 Clean any spilled water. 8 To install the new water flow sensor, see "4.21.2 Repair procedures" [  238]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 240 "5.3.2 Repair procedures" [  269]. Is the problem solved? Action No further actions required. Return to the troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 241: Water Pressure Sensor

    0 0.5 a Pressure (bar) b Output voltage (V) V DC Detected pressure (bar) 0.00 0.13 0.26 0.40 0.53 0.66 0.80 0.93 1.06 1.20 1.33 1.46 1.59 1.73 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 242 1–2 (= water pressure output). 8 Check that the measured voltage is in line with the expected voltage through the measured water pressure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 243: Repair Procedures

    4 To install the water pressure sensor wiring harness, see "4.22.2  Repair procedures" [  243]. To install the water pressure sensor wiring harness 1 Connect the wiring harness to the connector X7Y. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 244 To install the water pressure sensor 1 Check that a new O-ring is installed on the water pressure sensor. 2 Screw the water pressure sensor in the coupling piece. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 245: Water Pump

    Prerequisite: Stop the unit operation via the user interface. Prerequisite: Turn OFF the respective circuit breaker. Prerequisite: Remove the required plate work, see "4.16 Plate work" [  202]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 246 When the water pump is active and the connector PWM is disconnected from the PCB, the water pump motor will run at full speed. 6 Check if the pump is working (by listening or by touching the pump). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 247 14 Remove the cap from the PWM signal connector and measure the PWM signal between the PWM‑GND. ▪ When using an oscilloscope, the measured signal MUST look like the illustration shown below: EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 248: Repair Procedures

    Prerequisite: Remove the water pump, see "4.23.2 Repair procedures" [  248]. 1 Remove any impurities or objects that may block the water pump. 2 Install the water pump, see "4.23.2 Repair procedures" [  248]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 249 5 To install the water pump motor, see "4.23.2 Repair procedures" [  248]. To install the water pump motor 1 Install the motor on the water pump housing. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 250 Prerequisite: Remove the required plate work, see "4.16 Plate work" [  202]. 1 Drain water from the water circuit, see "5.3.2 Repair procedures" [  269]. 2 Disconnect the connectors from the water pump motor. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 251 5 To install the water pump, see "4.23.2 Repair procedures" [  248]. To install the water pump 1 Install the water pump in the correct location. a Connector EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 252 (power supply and/or PWM signal) of the water pump. 3 Fix the wiring harness using new tie straps. Is the problem solved? Action No further actions required. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 253 Components Is the problem solved? Action Return to the troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 254: Third Party Components

    Prerequisite: Stop the unit operation via the user interface. Prerequisite: Turn OFF the respective circuit breaker. Prerequisite: Remove the required plate work, see "4.16 Plate work" [  202]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 255 Correct the wiring as needed. Is the problem solved? Action No further actions required. Return to the troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 256: Repair Procedures

    It is recommended to perform the checks in the listed order. To check if the stop valves are open Prerequisite: Remove the required plate work, see "4.16 Plate work" [  202]. 1 Remove the caps. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 257 (dirt or ice build up in case of humidity in the system). EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 258 Low pressure rises with lowering compressor output. Operating frequency To maintain low pressure, operating frequency increases on the capacity control. (Degree of overcharge) Proper amount Further overcharge EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 259 (refrigerant shortage). Operating frequency To maintain low pressure, operating frequency decreases on the capacity control. (Degree of shortage) Higher degree of Proper amount shortage EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 260 To perform a pressure test of the refrigerant circuit 1 Perform a pressure test in line with local legislation. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 261: Repair Procedures

     263] for more details. Is the problem solved? Action No further actions required. Return to the troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 262 1 See the installer reference guide for the correct procedure. Is the problem solved? Action No further actions required. Return to troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 263 3 Perform pump down operation, see installer reference guide for the correct procedure. 4 After 5~10  minutes (after only 1~2  minutes in case temperature <–10°C), close the liquid stop valve using a hexagonal wrench. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 264 Pressure (absolute) Boiling point Micron / Torr Mbar / Pa °C 760000 / 760 1013 / 101325 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 265: Water Circuit

    3 Activate air purge operation of the space heating/cooling circuit via the user interface and select pump speed "High", see installer reference guide for correct procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 266 1 Inspect the installation outside the unit and check for the presence of an external heat source. This may have an impact on the water temperature inside the unit. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 267 To check for a leaking field installed domestic hot water tap 1 Inspect the installation outside the unit and check for a leaking domestic hot water tap. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 268 Temperature drop found? Action Replace the clogged part, see "5.3.2 Repair procedures" [  269]. Return to the troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 269: Repair Procedures

    Prerequisite: Remove the required plate work, see "4.16 Plate work" [  202]. 1 Close the stop valves of the water circuit. 2 Open the air purge valves, see "5.3.2 Repair procedures" [  269]. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 270 To open the air purge valves of the water circuit Prerequisite: Stop the unit operation via the user interface. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 271  265]. 2 See "To open the air purge valves of the water circuit"  [   270] for detailed information about the unit air purge valves. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 272 Return to the troubleshooting of the specific error and continue with the next procedure. To repair the leak in the water circuit 1 Repair the leak in the water circuit. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 273: Manufacturer Components

    5.4.2 Repair procedures To adjust the manufacturer component 1 See the specific dealer manual to adjust your component. Is the problem solved? Action No further actions required. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 274: External Factors

    Adjust as needed. Is the problem solved? Action No further actions required. Return to the troubleshooting of the specific error and continue with the next procedure. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 275: Maintenance

    General maintenance/inspection checklist. Next to the maintenance instructions in this chapter, a general maintenance/inspection checklist is also available on the Daikin Business Portal (authentication required). The general maintenance/inspection checklist is complementary to the instructions in this chapter and can be used as a guideline and reporting template during maintenance.
  • Page 276: To Check The Pipe Heaters

    Below is an overview of the different pipe heaters and technical data. Also check "7.2 Wiring diagram" [  281] for more information. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 277 Maintenance d + e A EBLA04~08E2V3 + EDLA04~08E2V3 units a E6H b E9H c E10H d E11H e E12H EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 278 Maintenance d + e A EBLA04~08E23V3 + EDLA04~08E23V3 units a E6H b E9H c E10H d E11H e E12H EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 279 Resistance Current voltage 230 V AC 50 W 970 Ω 0.23 A 230 V AC 50 W 970 Ω 0.23 A E10H 230 V AC 16.6 W 3300 Ω 0.07 A E11H 230 V AC 33 W 1600 Ω 0.15 A E12H 230 V AC 33 W 1600 Ω 0.15 A EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 280: Technical Data

    See the installer reference guide on business portal for more information. 7.1.2 Detailed information setting mode: Remote controller See the installer reference guide on business portal for more information. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 281: Wiring Diagram

    Rectifier bridge Connector Connector Connector Fuse T 6.3 A 250 V FU1, FU2 Fuse T 3.15 A 250 V Fuse T 30 A 250 V Connector IPM* Intelligent power module Connector LED A Pilot lamp Reactor EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 282 The wiring diagram is delivered with the unit, located at the inside of the service cover. Translation of text on wiring diagram: English Translation (1) Connection diagram (1) Connection diagram Hydro Hydro module Outdoor Outdoor EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 283 Internal backup heater power supply terminal X10M Smart Grid terminal Earth wiring Field supply Several wiring possibilities Option Wiring depending on model Switch box Legend (4) Legend EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 284 R1T (A2P) * Ambient sensor ON/OFF thermostat R1T (A14P) * Ambient sensor user interface R2T (A2P) * External sensor (floor or ambient) * Domestic hot water thermistor EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 285 Options: On/OFF output Options: On/OFF output Space C/H On/OFF output Space cooling/heating On/OFF output Switch box (6) Options (6) Options 230 V AC Control Device 230 V AC control device EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 286 Only for wired On/OFF thermostat Only for wired On/OFF thermostat Only for wireless On/OFF thermostat Only for wireless On/OFF thermostat Only for *** Only for *** EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 287 * High voltage Smart Grid relay Safety contactor backup heater * Contactor booster heater Q1DI # Earth leakage circuit breaker Power supply transformer * Terminal strip (booster heater power supply) EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 288 Translation # Terminal strip (power supply at client side) Terminal strip (integrated backup heater power supply) X10M * Terminal (high voltage Smart Grid) Connector Terminal strip EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 289 A8P: X801M: 3-5 4 core Optional part for EWA*/EWYA* signal X5M: 15-16 A11P: X1B: 1-2 2 core Power limitation demand input 4 A8P: X801M: 4-5 signal 4D139354 A EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 290 The diagrams shown in this manual may be incorrect due to changes/updates to the unit. Correct diagrams are supplied with the unit and can also be found in the technical data book. 4D139355 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 291 The diagrams shown in this manual may be incorrect due to changes/updates to the unit. Correct diagrams are supplied with the unit and can also be found in the technical data book. 4D139355 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 292 The diagrams shown in this manual may be incorrect due to changes/updates to the unit. Correct diagrams are supplied with the unit and can also be found in the technical data book. 4D139355 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 293 The diagrams shown in this manual may be incorrect due to changes/updates to the unit. Correct diagrams are supplied with the unit and can also be found in the technical data book. 4D139355 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 294 Correct diagrams are supplied with the unit and can also be found in the technical data book. A11P X5M.11 P1P2 X5M.12 X5M.16 X5M.15 WLAN SD CARD Cartridge SW3 SW4 SW5 WLAN UART Interface Debug UART Interface 4D139355 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 295 - t° Q3DI Q3DI X15M OUTDOOR Hydro X14M X14M 3N~ , 400V , 6kW or 9kW 1N~ , 230V , 3kW or 6kW 4D139355 BUH Option (EKLBUHCB6W1) EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 296 The diagrams shown in this manual may be incorrect due to changes/updates to the unit. Correct diagrams are supplied with the unit and can also be found in the technical data book. X14M X15M EKLBUHCB6W1 4D139355 EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 297: Piping Diagram

    Heat exchanger Screw connection q 4‑way valve Flare connection r Accumulator Quick coupling s Compressor Brazed connection t Muffler u Gas stop valve with service port EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 298 Heat exchanger Connections: p 4‑way valve Screw connection q Accumulator Flare connection r Compressor Quick coupling s Muffler Brazed connection t Gas stop valve with service port EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 299: Component Overview

    Inlet water thermistor R4T l Refrigerant pressure sensor S1NPH z Water pressure sensor B1PW m Manual air purge valve aa Water flow sensor B1L n Expansion vessel EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 300 Accumulator m Compressor M1C f Liquid service port n Muffler g Gas service port o Fan motor M1F h 4‑way valve coil Y1S p Fan EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 301: Component Overview: Single Phase Without Backup Heater

    Water pressure sensor B1PW j Plate type heat exchanger v Drain valve k Refrigerant pressure sensor S1NPH w Water flow sensor B1L l Automatic air purge valve EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 302 Accumulator m Compressor M1C f Liquid service port n Muffler g Gas service port o Fan motor M1F h 4‑way valve coil Y1S p Fan EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 303: Component Overview: Backup Heater Kit

    Switch box d Backup heater contactor K5M j Outlet water after backup heater thermistor R2T e Overcurrent fuse F1B k Backup heater f Terminal strip X15M EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 304: Field Information Report

    Technical data 7.5 Field information report See next page. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 305 In case a problem occurred on the unit which could not be resolved by using the content of this service manual or in case you have a problem which could be resolved but of which the manufacturer should be notified, we advise you to contact your distributor.
  • Page 306 Application information Application (house, apartment, office,…): New project or reimbursement: Heat emitters (radiators / under floor heating / fan coils /…): Hydraulic layout (simple schematic): Unit / Installation information Model name: Serial number: Installation / commissioning date: Software version hydro PCB A1P Software version hydro PCB A5P Software version user interface: Software version outdoor PCB:...
  • Page 307: Service Tools

    Technical data 7.6 Service tools 1 For an overview of the available service tools, check the Daikin Business Portal (authentication required). 2 Go to the tab After-sales support on the left navigation pane and select Technical support. 3 Click the button Service tools. An overview of the available service tools for the different products is shown.
  • Page 308: Field Settings

    Technical data 7.7 Field settings See next page. EBLA04~08E + EDLA04~08E Service manual Daikin Altherma 3 M ESIE22-09 – 2022.05 draft – 31/05/2022 15:53...
  • Page 309 1/14 Field settings table Applicable indoor units EBLA04E23V3 EDLA04E23V3 EBLA06E23V3 EDLA06E23V3 EBLA08E23V3 EDLA08E23V3 EBLA04E2V3 EDLA04E2V3 EBLA06E2V3 EDLA06E2V3 EBLA08E2V3 EDLA08E2V3 Notes (*1) EBLA* (*2) EDLA* (*3) *23V3 (*4) *2V3 4P685235-1 - 2022.03...
  • Page 310 2/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value Room └─ Antifrost 1.4.1 [2-06] Activation 0: No 1: Yes 1.4.2 [2-05] Room setpoint 4~16°C, step: 1°C 12°C └─ Setpoint range 1.5.1 [3-07] Heating minimum...
  • Page 311 3/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value └─ Modulation 2.C.1 [8-05] Modulation 0: No 1: Yes 2.C.2 [8-06] Max modulation 0~10°C, step: 1°C 5°C Main zone WD curve type 0: 2-points 1: Slope-Offset Additional zone...
  • Page 312 4/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value [9-0D] Pump speed limitation 0~8, step:1 0 : No limitation 1~4 : 90~60% pump speed 5~8 : 90~60% pump speed during sampling 6 80% pump speed Space heating / cooling...
  • Page 313 5/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value Installer settings └─ Configuration wizard └─ System 9.1.3.2 [E-03] BUH type R/O (*3) 0: No heater (*4) R/W (*4) 1: External heater 2: 3V (*3) 9.1.3.3 [E-05]...
  • Page 314 6/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value 9.1.8.1 [2-0D] Emitter type 0: Underfloor heating 1: Fancoil unit 2: Radiator 9.1.8.3 Setpoint mode 0: Fixed 1: WD heating, fixed cooling 2: Weather dependent 9.1.8.4 Schedule...
  • Page 315 7/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value └─ Booster heater 9.4.1 [6-02] Capacity 0~10kW, step: 0,2kW 9.4.3 [8-03] BSH eco timer 20~95 min, step: 5 min 50 min 9.4.4 [4-03] Operation...
  • Page 316 8/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value 9.A.2 [D-09] Electricity meter 2 / PV meter 0: No 1: 0,1 pulse/kWh 2: 1 pulse/kWh 3: 10 pulse/kWh 4: 100 pulse/kWh 5: 1000 pulse/kWh 6: 100 pulse/kWh (PV meter) 7: 1000 pulse/kWh (PV meter)
  • Page 317 9/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value [1-03] Leaving water value for high ambient temp. for LWT main zone [9-01]~min(45, [9-00])°C , step: 1°C heating WD curve. [2-0C]=0 25°C [2-0C]=1...
  • Page 318 10/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value [3-0A] What is the pump model 0: pump model 0 1: pump model 1 [4-00] What is the BUH operation mode? 0: Restricted 1: Allowed 2: Only DHW...
  • Page 319 11/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value [6-0E] What is the maximum temperature setpoint? E-07 = 0 40~ 60°C, step: 1°C 60°C E-07 = 3 40~ 75°C, step: 1°C 75°C E-07 = 5 40~ 80°C, step: 1°C...
  • Page 320 12/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value [9-0C] Room temperature hysteresis. 1~6°C, step: 0,5°C 1 °C [9-0D] Pump speed limitation 0~8, step:1 0 : No limitation 1~4 : 90~60% pump speed 5~8 : 90~60% pump speed during sampling 6 80% pump speed...
  • Page 321 13/14 Installer setting at variance with Field settings table default value Breadcrumb Setting name Range, step Date Value Default value [E-07] What kind of DHW tank is installed? 0 OSO tank 150/180 1 FS with BUH 2 FS with BSH 3 OSO tank 200/250/300 4 Rotex without BSH (HYB) 5 Rotex with BSH...
  • Page 322 14/14...
  • Page 324 ESIE22-09 2022.05 Verantwortung für Energie und Umwelt draft – 31/05/2022 15:53...

Table of Contents