6.6.4 BBR16 power limitation

EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
If... has priority
Space heating
2
Turns OFF all electrical heaters.
3
Limits the outdoor unit.
4
Turns OFF the outdoor unit.
Example
If the configuration is as follows:
Power limitation level does NOT allow operation of both booster heater and
backup heater (step 1 and step 2).
Priority heater = Booster heater (if applicable).
Then power consumption is limited as follows:
P
h
d
c
b
a
A
B
C
P
Produced heat
h
C
Consumed energy
e
A Outdoor unit
B Booster heater
C Backup heater
a Limited outdoor unit operation
b Full outdoor unit operation
c Booster heater turned ON
d Backup heater step 1 turned ON
e Backup heater step 2 turned ON
INFORMATION
Restriction: BBR16 settings are only visible when the language of the user interface is
set to Swedish.
NOTICE
2 weeks to change. After you activated BBR16, you only have 2 weeks to change its
settings (BBR16 activation and BBR16 power limit). After 2 weeks, the unit
freezes these settings.
Note: This is different from the permanent power limitation, which is always
changeable.
Use the BBR16 power limitation when you must comply with BBR16 regulations
(Swedish energy regulations).
You can combine the BBR16 power limitation with the other kW power
consumption controls. If you do so, the unit uses the most restrictive control.
Then set the priority heater via the
Backup heater
Result: The booster heater (if
applicable) will be turned OFF first.
e
C
e
6
Application guidelines
|
user interface to...
Installer reference guide
57