Henny Penny FlexFusion Platinum Installation Manual page 27

Electric combi team
Table of Contents

Advertisement

CAUTION
CAUTION
INFORMATION
Permanent connection
Risk of property damage and personal injury from improper instal-
lation
• In the case of a permanent connection, install an all-pin separating device
before the unit.
Install an all-pin separating device if the unit will be connected
permanently to the electrical supply mains.
Plug-in connection
Risk of property damage and personal injury from improper instal-
lation
• The plug-in connection must be readily accessible.
If the unit is connected with a plug to the electrical supply mains, use
plugs and sockets according to IEC60309.
The socket must be readily accessible so that the unit can be
disconnected from the electrical supply mains at any time.
Each unit must be connected individually.
Do not join the connection lines.
Insulation monitoring
In the case of an unearthed network (IT network), the unit can be
incorporated into the insulation monitoring.
Fault current device
Image: RCD switch type A circuit symbol
The unit can be connected to a fault current device.
If a residual-current circuit breaker is used, the residual-current circuit
breaker installed must be type A (RCD type A ) to ensure that AC fault
currents and pulsating DC fault currents are detected.
Installation instructions
Connecting the unit
27

Advertisement

Table of Contents
loading

Table of Contents