5.3 Control of "STO" and "SS1" via terminals on the Control Unit and the Motor/Power Module
Terminal
14
Max. connectable cross-section: 1.5 mm
DI: Digital input; DI/DO: Bidirectional digital input/output; M: Electronics ground; M1: Reference ground
1)
The rapid inputs can be used as probe inputs or as inputs for the external zero mark
2)
Data for: V
= 24 V; Load 48 Ω; High ("1") = 90% V
3)
cc
The maximum cable length that can be connected is 30 m.
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to function, terminal M1 must be connected.
This is achieved by using one of the following measures:
1. Route the ground reference for the digital inputs
2. A jumper to terminal M
Note: This removes isolation for these digital inputs.
Note
If the 24 V supply is briefly interrupted, then the digital outputs are deactivated during this
time.
Safety Integrated
Function Manual, 08/2023, A5E03264275A
Designation
Technical data
1)
"1" signal: 15 ... 30 V
M
"0" signal: -3 ... +5 V
Input current
at 24 V DC: typ. 3.5 mA
at <0.5 mA: Signal "0" reliably detected
Input delay
for "0" → "1": typ. 5 μs
for "1" → "0": typ. 50 μs
DI 8, DI 9, DI 10 and DI 11 are "fast inputs"
As output:
Voltage: 24 V DC
Electrical isolation: no
Reference potential: M
Output voltage
"1" signal, with load: > X124.+ -2 V
Output current
for each output: ≤ 0.5 A
Sum of all four outputs: ≤ 2 A
Residual current for "0" signal: < 0.5 mA
Short-circuit protection, automatic restart after a short-circuit
Load types: ohmic, capacitive, inductive
Output delay
for "0" → "1": typ. 150 μs / max. 400 μs (ohmic load)
for "1" → "0": typ. 75 µs / max. 100 µs (ohmic load)
Switching frequency
for ohmic load: max. 100 Hz
for inductive load: max. 0.5 Hz
for lamp load: max. 10 Hz
Lamp load: max. 5 W
2
out
3)
; Low ("0") = 10% V
out
Controlling the safety functions
2)
67