Beko QWIK-PURE 15 Installation And Operation Manual page 119

Table of Contents

Advertisement

Installation and operation manual
Error or fault pattern
FAULT 5
Illogical sensor values
(e.g. High Level (HL) sensor and 
High Level Alarm (HLA) sensor 
covered but Low Level (LL) 
sensor uncovered)
FAULT 6
Low Level (LL) sensor remains 
covered for too long after a
discharge process has been
started
Possible cause
1. Soiled FRC sensors
2. Very large quantity of oil in the
measuring chamber due to a
large oil inflow (e.g., oil leaking)
1. Soiled FRC sensors
2. Excessively low compressed air
operating pressure
3. The minimum compressed air
operating pressure is being
fallen below during operation
4. Filter cartridges are clogged
5. During the discharge operation,
a hissing sound can be heard at
the FRC pressure relief valves.
6. Piston malfunction
7. Riser duct clogged
Measure
Clean the FRC sensors (see section 
"10.3.5 Cleaning" on page 98)
Observe whether the error
message disappears after a few
discharge cycles
Clean the FRC sensors (see section 
"10.3.5 Cleaning" on page 98)
Select correct pressure range (see 
section "4. Technical data" on
page 32)
Check compressed air volume
Replacing filter cartridges (see 
section "10.3.2 Replacing filter 
cartridges" on page 84)
Remove PISTON Service-Unit
and check whether it is working
properly (see section "10.3.4
Replacing the piston" on
page 94) 
Clean or replace the riser duct
QWIK-PURE
®
119 | 124