4.6.5 To install the switch box

Service manual
64
A FAA71B unit
a Wiring terminal X2M
b Wiring terminal X1M
c Screw (cover)
d Cover
e Screw (ground wire)
f Indoor unit main PCB
g Screw (switch box)
h Switch box
A
A FAA100B unit
a Wiring terminal X2M
b Wiring terminal X1M
c Screw (cover)
d Cover
e Screw (ground wire)
f Indoor unit main PCB
g Screw (switch box)
h Switch box
3 Pull the clip and remove the 2 heat exchanger thermistors from their holder.
4 Remove the screw and remove the cover.
5 Remove the screw to disconnect the ground wire from the heat exchanger.
6 Disconnect the connectors of the indoor unit fan motor and the swing flap
motor(s) from the indoor unit main PCB.
7 Detach these wiring harnesses from the switch box.
8 Remove the screw and remove the switch box from the indoor unit.
9 To install the switch box, see
1 install the switch box in the correct location on the indoor unit.
c
d
f
e
g
"4.6 Plate
work" [
h
a
b
4
 60].