7
|
Technical data
7.7 Field settings
7.7.1 To retrieve the field settings
Via the wired remote controller BRC1E
Service manual
104
INFORMATION
Images are in English and for reference ONLY. For more details on the BRC1E please
refer to the user manual.
To access the field settings screen
#
1
Go to the basic screen.
2
Press at least 4 seconds while the
backlight of the screen is lit.
3
Select Field Settings.
4
Press.
In case of individual setting per indoor unit
#
1
Highlight the Mode.
Select the desired Mode No.
2
When Mode No. such as 20, 21,
22, 23, 25 are selected, highlight
the Unit No..
Select the Indoor unit No. to be
set.
Action
The Service Settings menu is
displayed.
The Field Settings screen is
displayed.
Action
The desired field setting mode is
selected.
▪
▪
▪
Result
Cool
Set to
28
°C
Service Settings
1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
Return
Setting
Result
The indoor unit for which you
want to set the field settings is
selected.
Current settings are displayed.
Second Code No. "-" means no
function.
Field Settings
Unit No.
Mode
0
20
Return
Setting
FAA71+100BUV1B
Sky Air indoor units
ESIE22-01 – 2022.02