To install the thermistor
FAA71+100BUV1B
Sky Air indoor units
ESIE22-01 – 2022.02
a Clip
b Thermistor
c Thermistor holder
4 Remove the thermistor from the thermistor holder.
5 Cut all tie straps that fix the thermistor harness.
6 Disconnect the thermistor connector from the appropriate PCB and remove
the thermistor.
7 To install the thermistor, see
Indoor unit air (room) thermistor
1 Install the air thermistor in the correct location on the switch box. Fix the
thermistor using a new tie strap.
b
a
a Tie strap
b Air thermistor
2 Route the thermistor harness through the appropriate retainers towards the
indoor unit main PCB.
3 Connect the thermistor harness to the indoor unit main PCB.
WARNING
When reconnecting a connector to the PCB, make sure to connect it on the correct
location and do NOT apply force, as this may damage the connector or connector
pins of the PCB.
b
c
a
"4.9.2 Repair
procedures" [
4
Components
|
4
 80].
Service manual