Repair procedures
To remove the swing flap motor
FAA71+100BUV1B
Sky Air indoor units
ESIE22-01 – 2022.02
Unit
FAA71B
FAA100B
Swing flap motor resistance
measurements are correct?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Remove both swing flaps from the indoor unit (by clicking it out).
2 Remove the screw (class 71) or 3 screws (class 100) from the swing flap
motor.
Pins
1‑2
1‑3
1‑4
1‑5
2‑3
2‑4
2‑5
3‑4
3‑5
4‑5
1‑2
1‑3
1‑4
1‑5
2‑3
2‑4
2‑5
3‑4
3‑5
4‑5
Action
Replace the swing flap motor wiring
harness, see
procedures" [
Replace the swing flap motor, see
"Repair
procedures" [
4
Components
|
Measured resistance (Ω)
325.5~374.5
602~798
353.4~406.6
653.6~866.4
"Repair
4
71].
4
71].
4
"4.6 Plate
work" [
60].
Service manual
71