Daikin Sky Air FAA71BUV1B Service Manual page 70

Indoor units
Hide thumbs Also See for Sky Air FAA71BUV1B:
Table of Contents

Advertisement

4
|
Components
Service manual
70
Unit
FAA71B
FAA100B
Swing flap motor resistance
measurements are correct?
Yes
No
3 Remove the swing flap motor, see
4 Measure the resistance between the following pins of the connector on the
swing flap motor.
Result: The measurements MUST be as shown in the table below.
Pins
1‑2
1‑3
1‑4
1‑5
2‑3
2‑4
2‑5
3‑4
3‑5
4‑5
1‑2
1‑3
1‑4
1‑5
2‑3
2‑4
2‑5
3‑4
3‑5
4‑5
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Continue with the next step.
"Repair
procedures" [
Measured resistance (Ω)
325.5~374.5
602~798
353.4~406.6
653.6~866.4
4
 75].
FAA71+100BUV1B
Sky Air indoor units
ESIE22-01 – 2022.02