Daikin Sky Air FAA71BUV1B Service Manual page 113

Indoor units
Hide thumbs Also See for Sky Air FAA71BUV1B:
Table of Contents

Advertisement

st
Setting
1
code
12/22
0
Output signal X1‑X2 of the optional KRP1 PCB kit
1
External ON/OFF (T1/T2 input) = setting when forced
ON/OFF is operated from outside.
3
Fan speed Thermo OFF heating mode
4
Differential ("D") for automatic changeover.
Temperature difference between cooling setpoint and
heating setpoint in automatic mode. Differential is
cooling setpoint minus heating setpoint.
5
Auto-restart after power failure
6
Fan speed Thermo OFF cooling mode
FAA71+100BUV1B
Sky Air indoor units
ESIE22-01 – 2022.02
nd
Description function
2
code
01
02
03
04
01
02
03
01
02
03
04
01
02
03
04
05
06
07
08
09
01
02
03
01
02
03
04
Description setting
Indoor unit Thermo ON Output
Option
Operation Output
Malfunction Output
Forced OFF
ON/OFF Operation
Emergency
LL
Set speed by remocon
OFF
Monitoring LL
0˚C (Default when HP Outdoor)
1˚C
2˚C
3˚C (Default when HR Outdoor)
4˚C (Default when VKM)
5˚C
6˚C
7˚C
Automatic control
Disabled
Enabled
Disabled in Japan.
Enabled in other countries.
LL
Set speed by remote controller
OFF
Monitoring LL
7
Technical data
|
Note
Service manual
113