5. Should the engine not start and run within three starting cycles, the LCD window will show the Fail to Start alarm
icon (
). The starting sequence may be repeated after the starter has had a minimum of two minutes to cool.
Pressing the Stop/Reset (O) button will clear the alarm and reset the controller.
6. Once the engine starts, it will immediately begin speeding up to a constant 1800 rpm. The engine may hunt or
change speeds until operating speed is reached. After a few minutes of operation, the engine will be warmed
up and the operator screens will show engine and generator operating parameters. The animated engine running
icon (
) will be displayed.
7. Check the generator for excessive noise or vibration and any coolant, oil, or fuel leaks before applying any loads.
8. Check that the frequency (Hz) is correct on the Generator screen. With no loads connected to the generator,
the frequency should read approximately 60 Hz, depending on the type of engine governing used.
9. Once the engine is running, allow it to reach normal operating temperature before switching on any loads.
10. If all wiring connections have been made correctly, switch the main circuit breaker to the ON (I) position and then
add any loads attached to the receptacles by switching the respective circuit breaker to the ON (I) position. You
will notice a slight change in engine sound when a load is applied to the unit.

AUTO (REMOTE) STARTING OF THE UNIT

Auto mode is used when the unit is started from a location other than the control panel by using a transfer switch.
Auto (remote start) is the normal setting when the generator is being used as a standby power supply. Before putting
the unit in the Auto mode, review the
Follow any warnings and information on isolating the generator with a transfer switch if the unit is to be used as a
standby power supply. Then continue with the steps described below:
1. Perform a manual start of the unit at least once to verify that the engine is operating correctly.
Note: The lights are automatically disconnected on startup. The main circuit breaker can be left on if no other loads
are connected, except for the lights. Any connected external loads must be disconnected by a transfer switch when
starting the unit.
2. If a check of the remote start circuit is desired:
a. Remove the wires from the remote start terminal block. Press the Auto button. The Auto LED with be lit.
b. Attach a jumper wire (minimum 16 gauge) across the two terminals on the remote start terminal block.
This applies a ground to the L401 controller to close the starting circuit contacts. The engine should
crank, start and run.
c. Remove the jumper wire from the remote start terminal block and the engine will stop.
d. Reconnect any necessary wires from the remote start switch (transfer switch) to the remote start terminal
block.
3. Confirm the unit is in Auto mode. The Auto LED should be lit.
4. Secure the unit by closing and locking all access doors.
5. The unit is now ready for remote starting.

AUTOMATIC SHUTDOWN

This unit is equipped with a low oil pressure and high coolant temperature automatic shutdown system. This system
will automatically shut off the fuel supply to stop the engine if oil pressure drops too low or the engine exceeds normal
operating temperature. Turn the Control Power switch to the OFF (O) position to reset the unit after you have
determined the cause of the shutdown.
Note: The unit will turn off the lights at the stop time, but the engine will continue to run for up to five minutes as a
cool down. If the Stop button is pressed, the unit will immediately stop.
"Prestart Checklist" on page 23
and
"Manual Starting of the Unit" on page
24.