levels.
FAILURE TO ISOLATE THE GENERATOR FROM THE NORMAL POWER UTILITY CAN
CAUSE POTENTIALLY LETHAL VOLTAGE TO BACKFEED INTO THE UTILITY LINES.
THIS MAY RESULT IN INJURY OR ELECTROCUTION OF UTILITY WORKERS NEARBY.
MAKE SURE THE GENERATOR IS ISOLATED BY A TRANSFER SWITCH FROM ANY
LOCAL UTILITY LINES. THIS ALSO APPLIES IF THE GENERATOR IS BEING USED
AS A BACKUP TO SOME OTHER TYPE OF POWER SUPPLY.
Installation of a transfer switch or other type of remote starting device is the responsibility of the generator user.
Installation of such devices must be performed by following all directions supplied by the manufacturer of the switch.
If attaching the generator to a power supply normally serviced by a utility company, notify the utility company and
check state and local regulations. Familiarize yourself with all instructions and warning labels supplied with the switch.
Incoming
Utility
Power
Utility
Meter
Power From
Generator
ONLY a licensed electrician should perform wiring or related connections to the
generator. Installation should be in compliance with the National Electrical Code
(NEC), state and local regulations. Failure to follow these procedures could result in
property damage, personal injury or death. Before any connections are attempted,
make sure the main circuit breaker and the Control Power switch are in the OFF (O)
position and that the negative (-) battery cable has been disconnected from the battery.
When using the generator as a standby or substitute power supply, make sure the output
voltage and phase rotation of the generator match those of the local power utility. Improper
voltage or phase rotation may cause equipment damage or malfunction.

AUTO EXERCISE TIMER

The L401 controller is capable of starting and stopping the unit automatically, based on a programmable schedule.
Units installed in a standby application should be exercised regularly to maintain operating condition and to ensure
responsiveness in an emergency situation. Use the following procedures to operate the unit in Auto mode:
Note: The controller MUST be in Auto mode to run at the programmed time. Use a trickle or solar battery charger
to prevent the controller from draining the battery while in Auto mode.
1. Push both the Stop/Reset (O) and Auto buttons simultaneously.
28
DANGER
Emergency
Distribution Panel
(Generator Power)
Main
Distribution Panel
(Utility Power)
Transfer
Switch
WARNING
WHITE = Incoming
Utility Power
GRAY = Normal Utility
Power Circuit
BLACK = Emergency
Generator Power Circuit
00206