Connecting SCALANCE M-800 to WAN
1.4 Adapting IP settings
1.4.1

Configuration with the Primary Network Initialization (SINEC PNI)

Introduction
The following section describes the procedure for using the SINEC PNI.
Requirement
● Device with factory settings
Procedure
1. Start SINEC PNI.
If several network cards are installed in the PC, select the network adapter connected to
SCALANCE M-800 in the "Settings" tab.
2. Click on the "Device List" tab in the navigation bar to switch to the "Device list" page.
3. Click the "Start network scan" button to scan the network for existing devices.
The scan settings configured on the "Settings" page are used. Adapt the settings
according to your needs if necessary. After the scan, all devices that can be configured
with the SINEC PNI are listed.
4. Select the checkbox in front of the device or multiple SCALANCE M-800 devices that you
want to configure and click the "Configure device" button.
The "Device configuration" dialog window is displayed.
5. Enter the desired IP address and the subnet mask of the selected device in the "IP
Configuration" tab. If you have selected multiple devices, in the "Start IP address" field
enter the first IP address of an IP address range, which is assigned to the selected
devices during loading.
Alternatively, you can select the DHCP option to have the IP address configuration of the
device performed by a DHCP server.
6. Enter further desired parameters in the tabs "System", "PROFINET", "Device Credentials"
and "PROFIBUS".
7. Click the "Load" button to transfer the configuration to the device.
18
Getting Started, 07/2020, C79000-G8976-C337-09
SCALANCE M-800