Hub Modules
7.4 DRIVE-CLiQ Hub Module External DME20
7.4.2.2

X500-X505 DRIVE-CLiQ interfaces

Table 7-6
Connector
type
The blanking covers for the DRIVE-CLiQ interfaces are included in the scope of delivery.
Blanking covers (6 units), article number: 6SL3066-4CA01-0AA0
Note
Only MOTION-CONNECT DRIVE-CLiQ cables may be used to establish connections.
The maximum length of MOTION-CONNECT 500 is 100 m and for MOTION-CONNECT 800PLUS
cables, 75 m.
7.4.2.3

X524 Electronics power supply

Table 7-7
3
5-pin socket,
max. connectable cross-section: 4 x 0.75 mm
Note
The maximum cable length for the 24 V supply of the DME20 is 100 m.
208
X500-X505: DRIVE-CLiQ interfaces
Pin
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
DRIVE-CLiQ socket
X524: Electronics power supply
Pin
Designation
1
Electronics power supply
2
2
Electronics power supply
5
1
3
Electronics ground
4
4
Electronics ground
5
not connected
Technical data
Transmit data +
Transmit data -
Receive data +
-
-
Receive data -
-
-
Power supply
Electronics ground
Technical data
The connection voltage of 20.4 V to
28.8 V refers to the (terminal) voltage at
the DME20. This must be taken into ac‐
count when selecting the cable cross-sec‐
tion and supply cable lengths.
Pins 1 and 2: jumpered internally
Pins 3 and 4: Bridged internally
Current consumption: max. 2.4 A
2
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2

Advertisement