Control Units and operating elements
4.3 Control Unit CU320-2 PN (PROFINET)
The maximum cable length that can be connected is 30 m.
Note
The two "+" or "M" terminals are jumpered in the connector. This ensures that the supply voltage
is looped through.
Note
The terminal block must be screwed on tightly using a flat-bladed screwdriver.
4.3.2.6

X127 LAN (Ethernet)

Note
Application
Ethernet interface X127 is intended for commissioning and diagnostics, which means that it
must always be accessible (e.g. for service).
Furthermore, the following restrictions apply to X127:
• Only local access is permissible
• No networking - or only local networking is permissible in a locked control cabinet
If remote access to the control cabinet is required, then additional security measures must be
taken to prevent misuse through sabotage, unqualified data manipulation and intercepting
confidential data (see also the Chapter "Industrial Security").
Table 4-6
Connector type: RJ45 socket
Note
The LAN interface does not support auto-MDI(X). If the LAN interface of the communication
partner also cannot handle auto-MDI(X), then a crossover cable must be used to establish the
connection.
56
X127 LAN interface (Ethernet)
Pin
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
Technical data
Ethernet transmit data +
Ethernet transmit data -
Ethernet receive data +
-
-
Ethernet receive data -
-
-
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2