Wiring and Installation

3.2 Output port wiring example

 Connect NPN (SINK) type load to R2-ECx004 output ports
3
The IO power (IO_24V / IOGND) and module power (24VPWR / PWR_GND) should be two
independent power circuits.
The following figure illustrates a single output point (Y00). The structure is the same for the
other 15 output points (Y01 - Y15). Connect the GND of the output port to IOGND to avoid
output status error. If an inductive load is connected, ensure to connect a flyback diode to both
sides of the inductive load in parallel to protect the output circuit.
SINK
WAR NING
3-4
Internal circuit
FBD: flyback diode
Follow these instructions for power supply and wiring to prevent any danger.
Use two independent 24 V
output points to ensure proper operation.
Use 26 - 18 AWG wires for wiring.
(External power supply)
IO_24V
Y00
FBD
Y15
GND
IOGND
power supplies for the module and the common input /
DC
R2-ECx004 User Manual