Wiring and Installation

3.1 Input port wiring example

 Connect NPN (SINK) type load to R2-ECx004 input ports
3
The IO power (IO_24V / IOGND) and module power (24VPWR / PWR_GND) should be two
independent power circuits.
The following figure illustrates a single input point (X15). The structure is the same for the other
15 input points (X01 - X14). The rated voltage is 24 V
port. Do not use a power supply exceeding 28.8 V
the module circuit.
3-2
IO power supply
24 V
DC
0V
24V
IOGND
Internal circuit
IO_24V
S/S
X00
Relay
X15
N.O
N.C
LPF: low-pass filter
RVP: reverse voltage protection
IOGND
Follow these instructions for power supply and wiring to prevent any danger.
Use two independent 24 V
output points to ensure proper operation.
Use 26 - 18 AWG wires for wiring.
for the input port and module power
DC
or an AC power supply to avoid damaging
DC
LPF
power supplies for the module and the common input /
DC
R2-ECx004 User Manual
Module power supply
24 V
DC
24V
0V
24V
GND
RVP
24VPWR
PWR_GND
SINK