7
The Advanced Settings will appear. Check the settings indicated by the red boxes.
EtherNet/IP connection is Enabled by default. Disable EtherNet/IP and set PROFINET to Enabled.
If the IP address needs to be changed (when connecting multiple V430s, for example), configure the
IP Address as needed for your application.
Communications Settings Procedure
To use PROFINET communication, the settings below must be configured.
Configure Network Settings of V430-F
Configure Default PROFINET Settings
Configure IO Supervisor (Computer)
Settings
• IP Address Settings
Configure IO Controller Settings
• IP Address Settings
• PROFINET IO System Settings
• IO Device Settings and Assignments
• Compile and Save Settings
Transfer Settings and Check Connection
• Check IO Controller Connection
• Transfer Parameters
• Check Connection Status
• Check Data Assignments
Memory Assignments
Refer to Appendix B – V430-F Input and Output Modules for the definition of input and output modules.
V430-F Series Autofocus Multicode Reader User Manual for Communication Settings
4 Controlling Operation and Data Output with PROFINET
Set in WebLink
Configure the settings with the engineering tool. If you are setting the
V430-F as an IO device, install a GSD file that defines the V430-F IO
data CR connection information in the engineering tool. The V430-F
GSD file can be downloaded from our website. For PROFINET IO
system settings, refer to applicable engineering tool manual(s).
Connect the computer (engineering tool), V430-F, and external
devices, and use the engineering tool to transfer settings and check
communication.
4
4-9