Controls Information

Controls Information
Series F1 & F2 Rental AHU
Controls
Rental AHU's with the F1 & F2 designator come equipped
with either a single or dual Trane TR2 VFD(s)
mounted in a control cabinet inside the unit. The VFD(s)
are controlled by using a single digital potentiometer
(Figure
31) that is located in a weatherproof box mounted
on the exterior of the unit, just above the disconnect. The
digital potentiometer is used to manually increase or
decreased the fan speed of the unit. For adjustment
purposes, the number '0000' on the Digital Potentiometer
represents the minimum fan setting 20 Hz, while '1000'
represents 100% nominal air flow.
Figure 30. Trane TR2 VFD
Figure 31. Digital Potentiometer

Series F0 Rental AHU Controls

Rental AHU's with the F0 designator come equipped with
a Trane MP-580 controller
(Figure
33) mounted in a control cabinet inside the unit.
38
(Figure
(Figure
32) and Trane TR-1 VFD
The controller is accessed by opening the external control
cabinet door with an emergency stop button.
The unit control program can be accessed using a laptop
computer with the Rover
unit-mounted stand alone display. The stand alone display
30)
is mounted in a sealed cabinet on the front of the unit next
to the external disconnect
display touch screen is an intuitive operator interface for
monitoring and changing unit control functions. With the
operator display you can:
Figure 32. MP-580 controller
Figure 33. TR1 VFD
Choose between "constant volume" or "VAV."
Choose specific air flow within specified range.
Monitor space temperature, air flow, filter status, etc.
Identify and troubleshoot problems.
View and reset controller alarms.
®
service tool software or the
(Figure
34). The operator