RSAU0025F1 AHU

Model Number ......................................................... TCCB
Water Connection Size ............................. 2.5 in Victaulic
Ambient Operating Conditions
Supply Motor............................................................ 25 hp
Fused Disconnect .........................................................Yes
Number of Electrical Circuits ..........................................1
Discharge Configuration.................................. Horizontal
Flex Duct Connection Size ............................ 19 in round
Number of Discharge Air Connections ..........................2
Max Discharge Static Pressure ........................6.0 in ESP
Number of Return Air Connectors..................................3
2
Filter Rack (Qty and size)
Nominal Air Flow (cfm) ..........................................10,000
3
Min/Max Air Flow (cfm)
Selection is required for actual AHU performance.
1
For ambient conditions below 40°F, glycol is recommended.
2
Unit provided with standard 2 in filters. Filter rack will accept up to 95%
efficient MERV 14 filters.
3
Min/Max airflow is dependent upon external static pressure requirement.
Contact Rental Services for specific airflow and static pressure information.
Electrical Data
Voltage ........................................................ 460V 3-phase
Frequency ..................................................................60 Hz
Lug(s) can accept wire up to ..................... #3 AWG wire
Minimum Circuit Ampacity (MCA) ................... 44 amps
Maximum Overcurrent Protection (MOP) ......... 70 amps
Provided with 50 ft of 4 conductor, 8 awg multicable
For additional electrical information, contact Trane Rental Services.
10
1
........................14–104°F
... (4) 24 in x 24 in, (2) 24 in x 12 in
..............................5,500/11,250
Performance Data
CFM
Air Pressure Drop through Unit (in H
Cooling Coil
Entering Air DB/WB Temp (°F)
Leaving Air DB/WB Temp (°F)
GPM
Entering Water Temp (°F)
Leaving Water Temp (°F)
Coil Water Pressure Drop (ft H
Sensible Capacity (MBH)
Total Capacity (MBH)
Coil Face Area (sq ft)
Coil Rows
Heating Coil
Entering Air DB/WB Temp (°F)
Leaving Air DB/WB Temp (°F)
GPM
Entering Water Temp (°F)
Leaving Water Temp (°F)
Coil Water Pressure Drop (ft H
Total Capacity (MBH)
Coil Face Area (sq ft)
Coil Rows
Water Flow Rates
CW Coil Flow (GPM)
CW Coil Pressure Drop (ft H
0)
2
HW Coil Flow (GPM)
HW Coil Pressure Drop (ft H
0)
2
Dimensions and Weights
Length
Width
Height
Weight
Width includes permanently mounted piping manifold.
Lifting Device: Fork Lift or Crane
10,000
0)
2.8
2
84/77
55/54.9
155
45
55
0)
8.53
2
323.9
778.8
19.9
8
45
78
36
180
160
0)
2.38
2
357.89
19.9
1
Minimum
Maximum
70
200
2.14
13.66
10
125
0.2
28.07
19 ft 0 in
6 ft 11 in
7 ft 6 in
8,350 lb
CHS-SVX02C-EN