Rsau0050F1 Ahu - Trane TCCA Accompaniment To The Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

RSAU0050F1 AHU

Model Number ......................................................... TCCB
Supply and Return Water Connection 
Sizes (inches) ...................................... 2.5 in Victaulic
Ambient Operating Conditions
Supply Motor.............................................................50 Hp
Fused Disconnect ......................................................... Yes
Number of Electrical Circuits .......................................... 1
Discharge Air Configuration............................. Horizontal
Flex Duct Connection Size.............................. 19 in round
Number of Discharge Air Connections ......................... 4
Number of Return Air Connections ................................ 5
Max Discharge Static Pressure ........................ 6.3 in ESP
2
Filters (Quantity and size)
Nominal Air Flow (cfm) .......................................... 20,000
3
Min/Max Air Flow (cfm)
Selection is required for actual AHU performance.
1
For ambient conditions below 40°F, glycol is recommended.
2
Unit provided with standard 2 in filters. Filter rack will accept up to 95%
efficient MERV 14 filters.
3
Min/Max airflow is dependent upon external static pressure requirement.
Contact Rental Services for specific airflow and static pressure information.
Electrical Data
Voltage ......................................................... 460V 3-phase
Frequency ..................................................................60 Hz
Minimum Circuit Ampacity (MCA) .................... 83 amps
Lug(s) can accept wire up to ..............................250MCM
Maximum Overcurrent Protection (MOP) ....... 125 amps
Provided with 50 ft of 4 conductor, 4 awg multicable
For additional electrical information contact Trane Rental Services.
16
1
...................... 14 – 104°F
....(9) 24 in X 24 in (3) 24 in x 12 in
.............................. 8,500/22,250
Performance Data
CFM
Air Pressure Drop through Unit (in H
Cooling Coil
Entering Air DB/WB Temp (°F)
Leaving Air DB/WB Temp (°F)
GPM
Entering Water Temp (°F)
Leaving Water Temp (°F)
Coil Water Pressure Drop (ft H
Sensible Capacity (MBH)
Total Capacity (MBH)
Coil Face Area (sq ft)
Coil Rows
Heating Coil
Entering Air DB/WB Temp (°F)
Leaving Air DB/WB Temp (°F)
GPM
Entering Water Temp (°F)
Leaving Water Temp (°F)
Coil Water Pressure Drop (ft H
Total Capacity (MBH)
Coil Face Area (sqft)
Coil Rows
Water Flow Rates
CW Coil Flow (GPM)
CW Coil Pressure Drop (ft H
0)
2
HW Coil Flow (GPM)
HW Coil Pressure Drop (ft H
0)
2
Dimensions and Weights
Length
Width
Height
Weight
Width includes permanently mounted piping manifold.
Lifting Device: Fork Lift or Crane
20,000
0)
2.83
2
84/77
55/54.9
310
45
55
0)
14.29
2
647.8
1557.6
40.6
8
45
78
71
180
160
0)
3.56
2
715.77
40.6
Minimum
Maximum
100
350
2.03
17.82
20
185
0.31
22.71
21 ft 7 in
8 ft 6 in
9 ft 1 in
11,600 lb
CHS-SVX02C-EN
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents