Trane Tracer AdaptiView Installation Instructions Manual

Rtac rotary chiller display upgrade kit
Hide thumbs Also See for Tracer AdaptiView:

Advertisement

Quick Links

Installation Instructions
Tracer® AdaptiView™ RTAC Rotary
Chiller Display Upgrade Kit
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.
April 2020
SAFETY WARNING
RCDA-SVN002C-EN

Advertisement

Table of Contents
loading

Summary of Contents for Trane Tracer AdaptiView

  • Page 1 Installation Instructions Tracer® AdaptiView™ RTAC Rotary Chiller Display Upgrade Kit SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
  • Page 2 PRIOR to Practices servicing the unit. NEVER PERFORM ANY Trane believes that responsible refrigerant practices are SWITCHING, DISCONNECTING, OR VOLTAGE important to the environment, our customers, and the air TESTING WITHOUT PROPER ELECTRICAL PPE AND conditioning industry.
  • Page 3 Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
  • Page 4: Table Of Contents

    Table of Contents Model Number Descriptions Templates ....5 ......49 General Information .
  • Page 5: Model Number Descriptions

    Model Number Descriptions Digit 1, 2, 3 Digits 16-18 — Unit Nominal RCD= Rotary Chiller Display Upgrade Capacity 000 = Not Required Digit 4 — Development 120 = 120 Ton Nominal Capacity  Sequence RTAC unit Development Sequence 130 = 130 Ton Nominal Capacity ...
  • Page 6: General Information

    1-3/8” knockout punch (needed for enclosure option an older Tracer CH530 DynaView™ equipped RTAC ® only) Series R air-cooled chiller to a Tracer AdaptiView™ display system. • 1-1/4” hole saw or knockout punch (needed for Arm mount option only) Other Required Manuals •...
  • Page 7: Rtac Adaptiview™ Display Upgrade Kit Contents

    General Information RTAC AdaptiView™ Display Upgrade Kit Contents UC800/TD7 Upgrade Kit Kit Components — Standard Table 1. TD7 kit contents — 018800330100 Part Number Mnemonic Description Quantity X13651571010 MOD01924 Module; TD7 Display X19070632020 CAB01206 Sealed Ethernet Cable, 3700mm (12 ft) X19051625030 CAB01534 PWR Cable from TD7 to UC800 (Connector to Prepped End), 78.74”...
  • Page 8 General Information Table 6. Back plate assembly kit — 018800350100 Part Number Mnemonic Description Quantity 507118350001 RTAC UC800 Back Plate Assembly Back Plate Assembly Kit Components: X25330033200 SCR00891 Screw; Phillips Panhead, 0.375 in, thread rolling, zinc plate 8-32 507118340001 Back Plate, RTAC X13110674010 FUS01498 Fuse, Class CC FNQ-R 1A 600V...
  • Page 9: Optional Add-On Kits

    General Information Optional Add-On Kits Table 9. LonTalk kit — 018800430100 Part Number Mnemonic Description Quantity X13650845040 MOD02418 Module, COM5 Interface Table 10. Generic BAS LLIDs kit — 018800050100 Part Number Mnemonic Description Quantity X13650728070 BRD04873 Dual Low Voltage Input (ICE Making Control) X13650731070 BRD04875 Analog Input/Output, External Current Limit &...
  • Page 10 General Information Table 14. Global connector kit, 4-compressor units, base lengths 39 or 45 ft — 018800400100 Part Number Mnemonic Description Quantity X13790348080 TDR00354 Pressure Transducer X13650726100 SEN01959 Temperature Sensor X13540076010 RSN00002 Resin; Heat Conductive Compound, 4 oz. KIT13723 KIT13723 4-wire Ribbon to Global Connector Adapter X19051622010 CAB01146...
  • Page 11: Installation

    Installation Check the Configuration and Setpoints in the DynaView™ Display/Controller 1. Check the current configuration of the DynaView™ and confirm that all settings are correct. Make any necessary changes. 2. Check the current chiller set-points programmed into the DynaView and confirm that they are all correct for the unit.
  • Page 12: Shut Down Power

    1. Cover unit control cover back plate with plastic to inadvertently energized. For variable frequency drives or prevent metal chips intrusion. other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of NOTICE: capacitors.
  • Page 13: Td7 Enclosure Option

    Installation 4. On either the side or front control panel, drill one 7/8” TD7 Enclosure Option hole for the USB Service Port. 1. Use a 1-3/8” knockout punch to enlarge the 11/16” Note: Length from the USB port location to the back diameter hole used to route the Dynaview™...
  • Page 14 Installation Figure 9. Leveling enclosure and hole marking Figure 11. TD7 to enclosure backplate 7. Assemble the TD7 to the enclosure with #10-32 lock nuts. See Figure Figure 12. Assemble the TD7 to the enclosure 3. Remove the front panel or place a piece of wood in between the panel and condenser tubes before drilling any holes.
  • Page 15: Arm Mount Option

    Failure to follow instructions below could result in minor to moderate personal injury. The display arm is spring-loaded! Do not unfasten the Tracer AdaptiView display from the display arm for any reason without first decreasing the arm tension to its lowest setting!
  • Page 16: Adjusting The Tracer ® Adaptiview™ Display Arm

    3. Joints 1 and 2 are covered by a plastic cap. Remove the plastic cap to access the hex bolt. Adjust using a 13 mm wrench as necessary. 4. To adjust the swivel of the Tracer AdaptiView display (the spin right and left similar to the steering wheel on RCDA-SVN002C-EN...
  • Page 17: Back Plate Assembly

    Installation Back Plate Assembly NOTICE: 1. Using the 1/4-20 bolts, nuts and sealing washers Transformer Damage! secure the back plate assembly to the side panel. See Figure 20, p. Failure to follow instructions below could result in transformer damage. Be sure to connect fuse on back plate to correct terminal on the unit.
  • Page 18 Installation 6. Crimp two terminals (X19180041070) to extension X19051625030 from the TD7 and connect to the “Load” Figure 26. USB port installation Side of the transformer. See Figure 24, p. Figure 24. TD7 power connection Install USB Port Into Panel with Weatherproof Cap Connect TD7 Power and Connect...
  • Page 19: Restore System Power

    Installation Restore System Power To prevent an unexpected chiller start up when system power is first restored, implement the appropriate preventative measure from the following list: 1. If the chiller is equipped with an external Auto Stop button, disconnect the wire from terminal J2-1 on the 1U4 LLID.
  • Page 20: Programming The Tracer ® Adaptiview

    Failure to follow instructions below could result in damage to the controller. When doing any service work on a Tracer AdaptiView control system that requires connecting a laptop computer running Tracer TU service tool software to the UC800 controller, the laptop must be operated from a SEPARATE AC power source AT ALL TIMES.
  • Page 21 Installation Table 15. Mapping table (continued) Compressor Manufacturing Unit Type Unit Compressor CT Meter Frame Size Location (Model Number Digit 12) Voltage Scale M1,M3 Curitiba, Pueblo, Taicang H = High Efficiency M1,M3 Curitiba, Pueblo, Taicang N = Standard, A = Extra Efficiency M1,M3 Curitiba, Pueblo, Taicang H = High Efficiency...
  • Page 22 Installation Table 15. Mapping table (continued) Compressor Manufacturing Unit Type Unit Compressor CT Meter Frame Size Location (Model Number Digit 12) Voltage Scale N1,N3 Curitiba, Pueblo, Taicang N = Standard, A = Extra Efficiency N1,N3 Curitiba, Pueblo, Taicang H = High Efficiency N1,N3 Curitiba, Pueblo, Taicang N = Standard, A = Extra Efficiency...
  • Page 23 Installation Figure 30. Binding view for all LLIDs 8. Validate configuration and setpoint values from the 9. In the case you changed any configuration or setpoint Chiller Report PDF file that was created from values, click the Save button. This updates the values KestrelView.
  • Page 24: Options

    A folder will be created with the name New Folder; • Ice Making Status this can be renamed later. The path to the folder will • Customer Programmable Relays C:\Programs\Trane\TracerTU\Program\Plugins\UC ® Tracer Interface Control DataBaseDAL\New Folder f. Select the New Folder file.
  • Page 25 Installation Generic BAS Integration Table Figure 39, p. 32 component location and appropriate unit schematic for Generic BAS integration. Table 16. Generic BAS LLID description and connections Component LLID Description/ Mating Designation Mnemonic Part Number Description Connector Terminal(s) Function Connection Communication IPC BUS (WB..) (UC800)
  • Page 26 Description/ Mating Mnemonic Part Number Description Connector Terminal(s) Function Connection Link + To Building Automation System or other Trane Remote Device Link - (Shielded Twisted MOD01628 X13651144010 Tracer UC 800 Pair) Link + To Next Unit (Shielded Twisted Link - Pair) ®...
  • Page 27: Ifm Efector Flow Switch

    Figure 40, p. 34 Figure 41, p. checkout procedures. Thermal Dispersion Flow Switch Upgrade If you have further questions, contact Trane Global Parts Technical Services. To contact them, send a message to The thermal dispersion flow switch upgrade is a set of ATechnicalService@trane.com.
  • Page 28: Component Locations

    Component Locations Table 19. Global connection component index Device Part Number Description 3LL1 VARIABLE EVAPORATOR REFRIGERANT LIQUID LEVEL SENSOR, CIRCUIT 1 3PT1 X13790348080 SUCTION REFRIGERANT PRESSURE TRANSDUCER, CIRCUIT 1, COMPRESSOR 1A 3PT2 X13790348080 CONDENSER REFRIGERAND PRESSURE TRANSDUCER, CIRCUIT 1 3PT3 X13790348080 OIL PRESSURE TRANSDUCER, COMPRESSOR 1B 3PT4...
  • Page 29 Component Locations Figure 36. Component location, 2 compressor units RCDA-SVN002C-EN...
  • Page 30 Component Locations Figure 37. Component location, 3 compressor units RCDA-SVN002C-EN...
  • Page 31 Component Locations Figure 38. Component location, 4 compressor units RCDA-SVN002C-EN...
  • Page 32 Component Locations Figure 39. Component location, RTAC control panel RTAC CONTROL PANEL 1 1TB7 1U14 1U15 1U16 1U17 1TB1 1U19 1U21 1U22 1CB1 1F15 1SW1 1F16 1U27 1F17 1U13 1U26 1U12 1U25 1U23 1U10 1K14 1U24 RCDA-SVN002C-EN...
  • Page 33 Component Locations Page Left Intentionally Blank RCDA-SVN002C-EN...
  • Page 34: Wiring

    Wiring Kit Schematic Important: Optional efector flow switch connection at 1TB5 is 115V. Figure 40. RTAC UC800/Tracer AdaptiView upgrade schematic RCDA-SVN002C-EN...
  • Page 35 Wiring Important: Optional efector flow switch connection at 1TB5 is 115V. Figure 41. RTAC UC800/Tracer AdaptiView upgrade schematic (continued) RCDA-SVN002C-EN...
  • Page 36: Global Harness Routing

    Wiring Global Harness Routing Figure 42. Global harness wiring diagram — 2 compressor unit, 15 foot base RCDA-SVN002C-EN...
  • Page 37 Wiring Figure 43. Global harness wiring diagram — 2 compressor unit, 18 foot base RCDA-SVN002C-EN...
  • Page 38 Wiring Figure 44. Global harness wiring diagram — 2 compressor unit, 21 foot base RCDA-SVN002C-EN...
  • Page 39 Wiring Figure 45. Global harness wiring diagram — 3 compressor unit, 2-pass, 30 foot base RCDA-SVN002C-EN...
  • Page 40 Wiring Figure 46. Global harness wiring diagram — 3 compressor unit, 3-pass, 30 foot base RCDA-SVN002C-EN...
  • Page 41 Wiring Figure 47. Global harness wiring diagram — 3 compressor unit, 2-pass, 36 foot base RCDA-SVN002C-EN...
  • Page 42 Wiring Figure 48. Global harness wiring diagram — 3 compressor unit, 3-pass, 36 foot base RCDA-SVN002C-EN...
  • Page 43 Wiring Figure 49. Global harness wiring diagram — 3 compressor unit, 2-pass, 39 foot base RCDA-SVN002C-EN...
  • Page 44 Wiring Figure 50. Global harness wiring diagram — 3 compressor unit, 3-pass, 39 foot base RCDA-SVN002C-EN...
  • Page 45 Wiring Figure 51. Global harness wiring diagram — 4 compressor unit, 2-pass, 39 foot base RCDA-SVN002C-EN...
  • Page 46 Wiring Figure 52. Global harness wiring diagram — 4 compressor unit, 3-pass, 39 foot base RCDA-SVN002C-EN...
  • Page 47 Wiring Figure 53. Global harness wiring diagram — 4 compressor unit, 2-pass, 45 foot base RCDA-SVN002C-EN...
  • Page 48 Wiring Figure 54. Global harness wiring diagram — 4 compressor unit, 3-pass, 45 foot base RCDA-SVN002C-EN...
  • Page 49 Templates • Figure 55, p. 49 for arm mount hole template. • See document RCDA-SVN003*-EN for enclosure hole template. • Figure 56, p. 51 for back plate template. Figure 55. Arm mounting holes template, mm (in.) Note: Template is shown ACTUAL SIZE. RCDA-SVN002C-EN...
  • Page 51 Figure 56. Back plate template (in) — actual size RCDA-SVN002C-EN...