Rsau0062F0 Ahu - Trane TCCA Accompaniment To The Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

RSAU0062F0 AHU

Model Number ..........................................................TCCB
Water Connection Size ................................ 4 in Victaulic
Ambient Operating Conditions
Supply Motor............................................................ 50 Hp
Fused Disconnect ......................................................... Yes
Number of Electrical Circuits .......................................... 1
Discharge Configuration...................................Horizontal
Flex Duct Connection Size..............................19 in round
Number of Discharge Air Connections .......................... 4
Max Discharge Static Pressure ...................... 6.00 in ESP
Number of Return Air Connections ................................ 5
2
Filter Rack (Qty and size)
.. (12) 24 in x 24 in, (4) 12 in x 24 in
Nominal Air Flow (cfm) .......................................... 25,000
3
Min/Max Air Flow (cfm)
Selection is required for actual AHU performance.
1
For ambient conditions below 40°F, glycol is recommended.
2
Unit provided with standard 2 in filters. Filter rack will accept up to 95% efficient
MERV 14 filters.
3
Min/Max airflow is dependent upon external static pressure requirement. Con-
tact Rental Services for specific airflow and static pressure information.
Electrical Data
Voltage ......................................................... 460V 3-phase
Frequency ..................................................................60 Hz
Lug(s) can accept wire up to .......................... 2 awg wire
Minimum Circuit Ampacity (MCA) .................... 91 amps
Maximum Overcurrent Protection (MOP) ....... 100 amps
For additional electrical information contact Trane Rental Services.
Provided with 50 ft of 4 conductor, 4 awg multicable
22
1
...................... 14 - 104°F
............................ 11,000/27,500
Performance Data
CFM
Air Pressure Drop through Unit (in H
Cooling Coil
Entering Air DB/WB Temp (°F)
Leaving Air DB/WB Temp (°F)
GPM
Entering Water Temp (°F)
Leaving Water Temp (°F)
Coil Water Pressure Drop (ft H
Sensible Capacity (MBH)
Total Capacity (MBH)
Coil Face Area (sq ft)
Coil Rows
Water Flow Rates
CW Coil Flow (GPM)
Pressure Drop (ft H
0)
2
Maximum water side pressure is 150psi (2.31ft H20 = 1 psi)
Dimensions and Weights
Length
4
Width
Height
Weight
4
Width does not include field installed piping manifold.
Lifting Device: Fork Lift or Crane
25,000
0)
3
2
84/77
50/49.9
378
44
56
0)
12.26
2
949.3
2274.6
49.2
10
Minimum
Maximum
110
475
1.61
18.47
18 ft 2 in
8 ft 6 in
10 ft 1 in
10,500 lbs
CHS-SVX02C-EN