4.
At the front of the enclosure, do one of the following steps:
2U enclosures—Insert one Torx M5 (long) screw into the mounting hole on each side
to secure the enclosure to the rack. Tighten the screws to a torque level of 13 in-lbs.
4U enclosures—Insert two Torx M5 (long) screws into the mounting holes on each
side to secure the enclosure to the rack (on each side, one screw goes into the rail and
the other to the cage nut). Tighten the screws to a torque level of 13 in-lbs.
5.
At the rear of the enclosure, tighten the two T25 slot (short) hold-down screws on the sides
of the enclosure. Tighten the screws to a torque level of 13 in-lbs. See
Figure 62 Tighten the enclosure hold-down screws
NOTE:
tighten the hold-down screws.
6.
Reinsert the yellow panels on each side of the enclosure.
7.
Connect the power cables to the power supplies, connect the data cables, and then secure
them with cable straps.
WARNING!
8.
Remove the appropriate number of drive blanks from the front of the drive enclosure
9.
Add the storage drives to the front of the drive enclosure bays, starting from bay 0 and
continuing sequentially.
10. To ensure proper thermal control, install blank filler panels into any empty slots.
64
System Component Installation in Existing Rack
Due to limited access, use a short length or right angle Torx bit screwdriver to
Do not power on without completing the remainder of the physical installation.