Cisco XR 12410 Installation Manual page 221

Cisco systems router installation guide
Hide thumbs Also See for XR 12410:
Table of Contents

Advertisement

Appendix A
Technical Specifications
Table A-2
Description
Total AC Input Power
Rated input voltage
Rated input line frequency
Input current rating
Source AC service
requirement
Heat dissipation
(total maximum)
Redundancy
1. For each AC power supply module.
To ensure that the chassis configuration complies with the required power
Caution
budgets, use the on-line power calculator. Failure to properly verify the
configuration may result in an unpredictable state if one of the power units fails.
Contact your local sales representative for assistance.
Table A-3
Description
Total DC Input Power
Rated input voltage
Input current rating
OL-17441-01
AC Electrical Specifications
Value
3000 VA (volt-amps) per AC power supply
(2 AC power supplies per system)
1
200–240 VAC nominal (range: 180 to 264 VAC)
220–240 VAC (UK)
1
50/60 Hz nominal (range: 47 to 63 Hz)
50/60 Hz UK
1
15 A maximum @ 200 VAC
13 A maximum @220 to 240 VRMS (UK)
20 A North America; 16 A international;
1
13 A UK
2800 W@9,544 BTU/hour
2 AC power supply modules required for 2N
redundancy
DC Electrical Specifications
Value
2800 W per DC power entry module
1
–48 VDC nominal in North America
–60 VDC nominal in the European Community
(range: –40.5 to –72 VDC (–75 VDC FOR 5mS))
1
40 A maximum (2x)
Cisco XR 12410 and Cisco XR 12810 Router Installation Guide