Installing the CPM1

3-2-2 Panel/Cabinet Installation

Overheating
Electrical Noise
Accessibility
3-3

Installing the CPM1

3-3-1 CPM1 Orientation

30
Consider PC operation, maintenance, and surrounding conditions when instal-
ling the CPM1 in a panel or cabinet.
The operating temperature range for the CPM1 is 0_C to 55_C. Be sure that
there is adequate ventilation for cooling.
• Allow enough space for air circulation.
• Do not install the CPM1 above equipment that generates a large amount of
heat, such as heaters, transformers, or large resistors.
• Install a cooling fan or system when the ambient temperature exceeds 55_C.
Power lines and high-voltage equipment can cause electrical noise in the PC.
• Do not install the CPM1 in a panel or cabinet with high-voltage equipment.
• Allow at least 200 mm between the CPM1 and nearby power lines.
Ensure that the CPM1 can be accessed for normal operation and maintenance.
• Provide a clear path to the CPM1 for operation and maintenance. High-voltage
equipment or power lines could be dangerous if they are in the way during rou-
tine operations.
• The PC will be easiest to access if the panel or cabinet is installed about 3 to 5
feet off of the floor.
The CPM1 must be installed in the position shown below to ensure adequate
cooling.
Control panel
Fan
CPM1
Air vent
200 mm min.
CPM1
200 mm min.
Correct
Section 3-3