Test Run In Monitor Mode - Omron Sysmac CPM1 Operation Manual

Hide thumbs Also See for Sysmac CPM1:
Table of Contents

Advertisement

Programming Example

4-4-5 Test Run in MONITOR Mode

1, 2, 3...
84
3. Input the desired check level (0, 1, or 2). The program check will begin when
the check level is input, and the first error found will be displayed.
Note Refer to 5-5 Programming Errors for details on check levels.
4. Press the SRCH Key to continue the search. The next error will be dis-
played. Continue pressing the SRCH Key to continue the search.
The search will continue until an END instruction or the end of Program
Memory is reached.
If errors are displayed, edit the program to correct the errors and check the pro-
gram again. Continue checking the program until all errors have been corrected.
Switch the CPM1 in MONITOR mode and check the operation of the program.
1. Set the Programming Console's mode switch to MONITOR mode.
MONITOR
RUN
PROGRAM
2. Press the CLR Key to bring up the initial display.
3. Force-set the start input bit (IR 00000) from the Programming Console to
start the program.
MONTR
The cursor in the lower left corner of the display indicates that the force set is
in progress. The bit will remain ON as long as the Set Key is held down.
4. The output indicator for output 01000 will flash ten times if the program is
operating correctly. The indicator should go OFF after ten one-second
flashes.
There is a mistake in the program if the output indicator doesn't flash. In this
case, check the program and force set/reset bits to check operation.
00178CIRCUIT ERR
A
0
OUT
<MONITOR>
00000
CLR
00000
LD
LD
00000
^ OFF
00000
SET
ON
Section 4-4
00200
BZ
00000

Advertisement