System Operation and Functions
F3SG-RA
Limit switch 2
(N.C. Contact)
24 V
If the duration between when the muting input A is turned ON from the OFF state and when the muting
input B is turned OFF from the ON state is within T1max [ s ], the safety function of the F3SG-RA is
disabled. (Safety outputs are kept ON even if F3SG-RA is blocked)
Time t1 [ s ] for F3SG-RA to enter muting state is within the range shown below:
t1 < T1max. . . . . . . . . . . Equation (5)
The value of T1
 Timing Chart
Muting input A
(Limit switch1)
Muting input B
(Limit switch2)
Muting state
Beam state
F3SG-R
68
User's Manual
During muting
Limit switch1
(N.O. Contact)
ON: To muting input A
ON -> OFF: To muting input B
can be changed by the Configuration Tool.
max
ON
OFF
ON
OFF
80 ms max.
Enabled
Disabled
Unblocked
Blocked
ON
OSSD
OFF
Guard fence
Input time difference between muting inputs A and B
must be T1max or less
(initial setting is 4 s)
T1max [ s ] : Muting input time limit value (maximum)
T3 (0.1 s) max.
T3 (0.1 s) max.
T1max
T2 max.
T2 max.