System Operation and Functions
 End conditions
If any of the following condition is satisfied, the muting state is released.
• When a workpiece passes a muting sensor A or B and the exit-only muting delay time (4 s) passes.
• When a workpiece passes F3SG-R's detection zone and the muting end wait time (1 s:
configurable) passes.
• The duration of the muting state exceeds the muting time limit (60 s: configurable).
 Timing chart
Muting input A
(Muting sensor A1)
Muting input B
(Muting sensor B1)
Muting state
Beam state
OSSD
* This timing chart shows the case in which the muting state was released under the condition of T4 (1 s).
 Factory default setting
Variable
T1min
T1max
T2
T3
T4
T5
F3SG-R
60
User's Manual
T3 (0.1 s) max.
ON
OFF
T1min to T1max
ON
OFF
80 ms max.
Enabled
Disabled
Unblocked
Blocked
ON
OFF
Variable name
Muting input time limit value
0.1 s
(minimum)
Muting input time limit value
4 s
(maximum)
Muting time limit
60 s
Maximum allowable muting
0.1 s
signal interruption
Muting end wait time
1 s
Exit-only muting delay time
4 s
T3 (0.1 s) max.
T2 max.
T3 (0.1s) max.
T5 max.
Value
Minimum time difference between muting inputs A and B.
If the time difference between muting inputs A and B is smaller
than this value, a muting sequence error occurs.
Maximum time difference between muting inputs A and B.
If the time difference between muting inputs A and B is larger
than this value, a muting sequence error occurs.
The duration time of the Muting function. The Muting state is
cancelled if it continues for longer than this time limit.
Maximum duration of a signal interruption allowed in muting
inputs A and B.
Time difference from when the F3SG-RA is unblocked until the
Muting state is cancelled.
Time difference from when the signal of Muting input A or B is
turned OFF until the Muting state is cancelled.
T4 (1 s)
Description